Knowledge Base › Fluid Systems Error Case › Pump Running Dry from Low Level

Pump Running Dry from Low Level

E44-625 · Level Control Failure · Pump Low Level · ★★★

Problem Description

Running dry, cavitation

Root Cause

[Mechanism] A low liquid level makes the pump run dry.
[Calculation] A low level draws in air and cavitates the pump.
[Design Omission] No interlock, no make-up, and no inspection were provided, so the level drops low.

Corrective Solution

1) Provide a low-level interlock to stop the pump (stop at ≤10% of span), because the original low level (≤5%) let air into the pump suction and caused severe cavitation vibration at 7mm/s, and the interlock trips for protection, thereby protecting the pump;
2) Add automatic make-up (open the make-up valve below 20% level at a flow matched to the pump), because a low level runs the pump dry and make-up holds the level, thereby preventing dry running;
3) Verify the suction elevation (suction lift ≤NPSHr+0.5m), because a low level sucks air and controlling the elevation preserves the margin, thereby preventing cavitation;
4) Select a pump with an adequate NPSH margin (larger suction bore or double suction), because an inadequate margin runs dry and a sufficient one stays stable, thereby tolerating low levels;
5) Monitor the level with alarms (low alarm plus low-low interlock), because a low level runs the pump dry and the alarm gives warning, thereby allowing early make-up;
6) Listen for dry-running noise (check for abnormal pump noise or vibration velocity), because gradual dry running damages the pump and inspection catches it early, thereby allowing a preemptive stop;
7) Limit the draw-off rate to prevent a low level (reduce the pump frequency to ≤45Hz), because fast draw-off lowers the level and limiting the speed holds it, thereby preventing a low level;
8) Write the interlock and make-up into the control card, because the missing interlock was the root cause of the low level and freezing it into the control card enforces control.

Checklist

Reference

GB/T 13007-2011 Centrifugal pumps