MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Fluid Systems Error Case › Lightning Protection and Grounding Causing Reading Fluctuation

Lightning Protection and Grounding Causing Reading Fluctuation

E44-662 · Level Control Failure · Lightning protection · ★★

Problem Description

Lightning strike, reading jumps, false readings

Root Cause

[Mechanism] Lightning interference makes the reading jump.
[Calculation] The interference causes the jumping.
[Design Omission] No grounding, no shielding and no checks were provided — so the signal was disturbed.

Corrective Solution

1) Provide good grounding for lightning protection (ground grid resistance ≤4Ω): because the original high ground resistance (>10Ω) let lightning-induced surges in and made the reading jump ±0.3m, low resistance drains the current so interference drops and the measurement steadies;
2) Add shielded cable against interference (double-shielded cable with the outer shield grounded): because interference makes it jump and shielding blocks it, the reading is stable;
3) Fit surge protection (power and signal SPDs, residual voltage <1kV): because a strike makes it jump and damages it, the SPD clamps the voltage and protects the instrument;
4) Verify the ground resistance (measure annually ≤4Ω): because high resistance disturbs and checking keeps it low, the reading is stable;
5) Select an instrument with voltage withstand (withstand ≥2kV): because a strike damages it and the withstand rating protects it, it does not fail;
6) Check the grounding condition (inspect the connections quarterly): because gradual loosening increases interference and checking gives early warning, they are tightened in time;
7) Route away from lightning sources (antenna ≥3m from the lightning rod): because proximity disturbs and distance reduces it, the measurement steadies;
8) Write the grounding and shielding into the assembly card: the original lack of grounding was the root cause of the interference, so the card locks it in and assembly governs it.

Checklist

Reference

GB/T 17614.1-2008 Transmitters for use in industrial-process control systems

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL