E44-812 · Piping Supports and Thermal Expansion · Flange · ★★
Flange under bending, bolt leakage, cracking
[Mechanism] A flange with no support nearby is subjected to bending.
[Calculation] Bending makes the flange bolts unevenly loaded and the seal fails, causing leakage.
[Design Omission] The flange was neither supported nor aligned — so it must be supported.
1) Add a flange support against bending (add a support at the flange side to reduce the cantilever): because the original lack of support bent the flange, unevenly loaded the bolts and failed the seal with leakage, adding the support reduces bending;
2) Check the flange squareness (flange face perpendicular to the pipe axis within ≤1mm): because skewing bends and the check squares it, the alignment is checked;
3) Keep the bolt preload even (tighten diagonally and evenly, with consistent torque): because uneven tightening bends and evenness flattens it, even tightening is applied;
4) Control the pipe-weight sag (the support carries the pipe to reduce the flange load): because sag bends and control relieves it, the weight is controlled;
5) Monitor the bending condition (measure the flange-face parallelism, alarm on deviation): because progressive bending brings leakage closer and early awareness helps, bending is monitored;
6) Perform a load test (hydrostatic test to check the flange seal): because the original lack of testing left the bending undiscovered, the test reveals the leakage, so the load test is run;
7) Raise the flange rating (increase the pressure class to leave margin): because a weak flange cracks and a higher rating strengthens it, the rating is raised;
8) Write the added support and alignment check into the assembly card: the original lack of support was the root cause of the bending, so assembly controls the work and the flange is square.
GB/T 9124-2019 Steel pipe flanges