E44-852 · Throttling Noise and Vibration · Expansion valve · ★★
A DN32 thermal expansion valve with a refrigerant pressure drop of 1.0MPa produced throttling noise of 88dB(A) and body vibration
[Mechanism] The refrigerant is throttled and cooled through the narrow valve port, and the high-speed two-phase flow strikes the valve cavity, producing noise and chatter.
[Calculation] Valve-port velocity v=Q/A raises the post-throttling quality x, and the two-phase Mach number Ma>0.3; noise Lw∝Δp².
[Design Omission] No low-noise model selected, no silencer installed, no inlet-pressure stabilization.
1) Select a low-noise expansion design (a multi-hole pressure-evening trim instead of a needle type), since the original narrow port with two-phase Ma>0.3 gave 88dB(A), thus selecting the holes cuts the noise;
2) Verify the sound level (valve body ≤85dB(A)), since exceeding it disturbs and verification meets it, thus verifying sound;
3) Add a silencer (resistive, rated for low temperature), since the bare valve radiates 88dB(A) and silencing lowers it, thus silencing;
4) Steady the inlet pressure (a receiver before the valve to cut fluctuation), since fluctuation makes noise and steadying controls it, thus steadying pressure;
5) Monitor the noise (sound-level meter, alarm >85dB(A)), since gradual growth approaches the limit and early detection catches it, thus monitoring noise;
6) Run an acoustic test (measure Lw), since the lack of testing left the noise undetected and the test reveals the level, thus testing sound;
7) Control the opening to steady it (moderate operation, avoid full close), since changing conditions make noise and control steadies it, thus controlling the opening;
8) Write the model selection and silencing into the specification, since the original lack of selection is the root cause of noise and locking it in closes the loop, thus controlling it in the spec.
GB/T 17213.1-2015 Industrial-process control valves