Knowledge Base › Fluid Systems Error Case › Water Column Separation in a Siphon Pipe

Water Column Separation in a Siphon Pipe

E44-955 · Siphon and Backflow · Siphon Pipe · ★★★

Problem Description

Water column separation, break, hammer

Root Cause

[Mechanism] The local negative pressure at the highest point of the siphon pipe is lower than the vaporization pressure, so the water column breaks into segments, flow stops, and water hammer is induced.
[Calculation] The vacuum at the highest point is -92 kPa, lower than the vaporization pressure of -85 kPa; the water column breaks into 3 segments, and at the instant of flow stoppage Δp=ρcΔv reaches a 0.9 MPa water hammer.
[Design Omission] The liquid level was not maintained, the suction height was not checked, and no makeup flow was provided.

Corrective Solution

1) Install a slow-closing valve at the outlet to keep the liquid column continuous (closing time ≥10 s), because a sudden break makes the vacuum drop sharply and a slow close stabilizes it, thereby keeping the column unbroken;
2) Check the suction height ≤ the allowable 6.0 m (originally 7.2 m), because too high a lift means too much negative pressure and checking the height preserves it, thereby suppressing the negative pressure;
3) Add a makeup flow pipe at the high point (makeup water 0.05 m³/min to keep the pipe full), because a drop in liquid level breaks the column and makeup flow keeps it connected, thereby maintaining the liquid column;
4) Improve the sealing at the highest point to prevent air ingress (flange PN16, airtight at 0.6 MPa), because air ingress breaks the column and sealing keeps it connected, thereby preventing breakage;
5) Perform a water column test (verify no flow interruption, Δp≤0.3 MPa), because the design omitted the height check and the test confirms whether the column breaks, thereby determining the suction height from data;
6) Provide a vacuum gauge and alarm at the high point (<-85 kPa), because breakage first shows as low vacuum before water hammer, thereby monitoring the vacuum for early warning;
7) Control the operating suction height ≤6.0 m (adjust if exceeded), because a higher suction height causes breakage and controlling the height prevents hammer, thereby preventing breakage in operation;
8) Write liquid retention and height checking into the calculation sheet, because the root cause of water column separation is excessive negative pressure without liquid retention, so the calculation must govern to prevent breakage.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »