E45-014 · Installation Position and Orientation · Pressure Transmitter at the High Point of a Process Water Line · ★★
The tap is set at the highest point of the line; the transmitter reads 0.015MPa lower than the local gauge and drifts slowly, so interlocks trip easily
[Mechanism] Gas density is far below that of liquid; gas accumulating in the impulse line removes the equivalent pressure of that liquid column, so the reading is low.
[Calculation] The height difference between the impulse line and the process line is h = 1.5m; a gas column replacing the liquid column means Δp = ρgh = 1000×9.81×1.5 ≈14.7kPa ≈0.015MPa missing.
[Design Omission] The tap did not avoid the high point, no vent valve was provided, and no zero shift was made.
① Tap position: move the tap to the lower half of the line or the lowest-point side (was the highest point) → full liquid gives accurate transfer, eliminating the 0.015MPa low reading from gas trapped at the high point
② Downward slope: slope the tap line downward at ≥1:10 to the transmitter → the horizontal run traps gas; let it drain itself
③ Vent valve: fit a vent valve at the high point and vent periodically → gas builds up gradually and drifts the reading; clear it
④ Zero shift: apply a negative shift equivalent to 0.015MPa on the transmitter → the static head difference is fixed; make up the missing pressure
⑤ Local comparison: compare periodically with a local gauge (difference <0.5%) → drift is gradual; correct it early
⑥ Seal fluid: fill the impulse line with seal fluid to prevent drying → a changing liquid column drifts the zero; keep the zero stable
⑦ Pressurization test: pressurize at 0/0.1/0.3MPa to verify linearity → design often skips it; confirm by measurement
⑧ Make it stick: write the tap position and venting into the tap layout drawing → eliminates low readings from high-point gas at the source
GB/T 1226 Pressure gauges