E45-034 · Cables and Drag Chains · Three-Wire RTD Without Twisted Pair · ★★
The RTD signal line uses ordinary parallel wire without twisting; when a nearby contactor operates, the reading jumps by ±3℃, exceeding the ±0.5℃ control accuracy
[Mechanism] Two parallel cores form a large loop area that couples magnetic fields and induces a common-mode voltage, and the asymmetry between the two cores converts the common mode into differential-mode interference on the reading.
[Calculation] The loop area A≈ spacing×length=50mm×5m=0.25m²; with dB/dt≈0.1T/s the induced e=A·dB/dt=25mV, corresponding to ±3℃.
[Design Omission] Twisted pair was not used, and the loop area was not reduced.
① Switch to twisted pair: change the signal line to shielded twisted pair (lay length ≤25mm) → loop area cut to 1/20, induced e down to 1.2mV
② Choose the lay length: select a lay length ≤25mm for the signal frequency → better cancellation of high-frequency interference
③ Shielding: add a shield over the twisted pair with single-point grounding → further common-mode suppression
④ Institutionalize twisted pair: make it a mandatory item in the wiring diagram → eliminates parallel wire
⑤ Loop test: measure the reading jump when a nearby device operates (≤0.3℃) → confirm by measurement
⑥ Routing: avoid running the signal line parallel to high-current lines → less coupling
⑦ Filtering: add hardware filtering at the receiver → suppress residual noise
⑧ Maintenance: add to the wiring process card → prevent recurrence
GB/T 18268.3-2010 EMC requirements for measurement and control equipment