E45-062 · Cables and Drag Chains · 4-20mA over 500m with 0.5mm² · ★★
A 4-20mA signal sent 500m over 0.5mm² cable develops 35Ω of loop resistance, giving a 0.7V drop at full scale and degrading accuracy from 0.1% to 0.5%
[Mechanism] The resistance of thin cable accumulates over a long run; although 4-20mA is not very sensitive to loop resistance, the resulting voltage drop plus the load raises the full-scale error.
[Calculation] R=2×500×0.0175/0.5=35Ω, so the drop ΔU=20mA×35=0.7V, a large share of the supply voltage that degrades accuracy.
[Design Omission] The long-line resistance was not calculated, and the conductor size was not increased nor a transmitter used.
① Larger conductor: switch to 1.5mm² cable → R drops from 35Ω to 11.7Ω, the drop to 0.23V, and accuracy is restored
② Use a transmitter: convert the signal locally to digital and transmit it → no long-line resistance
③ Resistance check: specify R ≤ supply headroom/20mA in the selection → gatekeeping at the source
④ Institutionalize: make conductor size versus distance a mandatory item in the IO list → drawing gatekeeping
⑤ Accuracy test: measure the full-scale error (≤0.2%) → confirm by measurement
⑥ Supply: increase the supply headroom → tolerate the loop resistance
⑦ Isolation: add a signal isolator → long lines do not accumulate error
⑧ Maintenance: add to the quarterly checklist → periodic calibration
GB/T 3369.1-2008 Analogue signals for process control systems