E45-067 · Cables and Drag Chains · Multiple Shields with Commoned Ground · ★★★
The shields of 6 shielded cables are all twisted together and connected to the ground bar at a single point; ground-bar potential fluctuations crosstalk through the common shield, so the channel readings interfere with each other and jitter by ±1%
[Mechanism] Commoning several shields at one point ties all the signal shields together at the same potential, so ground noise from any one loop couples through the shared shield into the others and causes mutual interference.
[Calculation] With a common shield resistance R_s=1Ω, a loop ground noise of ΔV=10mV couples through the shared shield and crosstalks ±1% into the neighboring channel.
[Design Omission] The shields were not grounded independently per loop, and no isolated shield commoning was used.
① Separate grounds: ground each shield independently at one end (no commoning) → no crosstalk between channels
② Isolation: ground the shields of sensitive loops through an isolator → blocks mutual coupling
③ Star connection: when a common point is unavoidable, use a star single-point ground → reduces the shared impedance
④ Institutionalize: make the grounding method a mandatory item in the wiring diagram → drawing gatekeeping
⑤ Crosstalk test: inject noise into one channel and read the jitter on the neighboring channel (≤0.2%) → confirm by measurement
⑥ Separate runs: run each channel's shield independently → no bundling together
⑦ Filtering: add common-mode filtering to each channel → residual suppression
⑧ Maintenance: add to the EMC check card → inspect periodically
GB/T 18268.3-2010 EMC requirements for measurement and control equipment