E45-069 · Cables and Drag Chains · Signal + Servo in One Tray · ★★★
The signal cable and the servo power cable run 3m in parallel in the same tray, so servo start/stop couples through space and makes the position feedback jitter by ±3 pulses
[Mechanism] Running in parallel over a long distance in the same tray lets the magnetic field of the power line couple into the signal line along the whole run; the longer the parallel section, the more energy is coupled.
[Calculation] With 3m in parallel and mutual inductance M≈0.3μH, the servo di/dt induces e=M·di/dt≈0.3V, above the threshold, causing ±3 pulses of jitter.
[Design Omission] The two were not run in separate trays, the parallel length was not reduced, and there was no shielding.
① Separate trays: run signal and servo power in separate trays (≥200mm apart) → blocks coupling
② Reduce parallelism: cross the cables where possible to shorten the parallel length → less coupled energy
③ Shielded twisted pair: change the signal cable to shielded twisted pair grounded at one end → common-mode suppression
④ Institutionalize: make separate trays a mandatory item in the wiring drawing → drawing gatekeeping
⑤ Jitter test: read the feedback jitter during servo start/stop (≤1 pulse) → confirm by measurement
⑥ Partition: add a dividing plate inside the tray → further blocking
⑦ Filtering: add EMC filtering at the receiving end → residual suppression
⑧ Maintenance: add to the EMC check card → inspect periodically
GB/T 18268.3-2010 EMC requirements for measurement and control equipment