E45-071 · Cables and Drag Chains · Outdoor Joint Not Potted · ★★
The outdoor connector was not potted, so moisture wicked into the gaps between the conductors; insulation resistance fell from >100MΩ to 5MΩ with occasional malfunction
[Mechanism] With the connector unpotted there are gaps between the conductors; moisture wicks in by capillary action, lowering the inter-conductor insulation and raising the leakage current until malfunction occurs.
[Calculation] At 90% relative humidity, water seeping into the conductor gaps lowers the insulation resistance from >100MΩ to 5MΩ, and the leakage current exceeds the trip threshold.
[Design Omission] The connector was not potted and no moisture protection was applied.
① Potting: fill the connector cavity with silicone or epoxy sealant → blocks capillary seepage
② Moisture protection: coat the conductor ends with moisture-proof varnish → the gaps no longer absorb water
③ Institutionalize: make potting a mandatory item in the process card → drawing gatekeeping
④ Insulation test: measure the inter-conductor insulation after installation (≥100MΩ) → confirm by measurement
⑤ Drainage: lead the cable out downward from the joint → condensate drains away by itself
⑥ Inspection: check quarterly whether the insulation has dropped → catch progressive decline early
⑦ Rating: choose IP68 connectors → moisture-proof by design
⑧ Maintenance: add to the quarterly check list → inspect periodically
GB/T 4208-2017 Degrees of protection provided by enclosures (IP Code)