E45-094 · Signal Interference and EMC · Analog Temperature Acquisition · ★★
A temperature AI run in the same trench as power cables shows ±0.3℃ spikes every cycle (20ms)
[Mechanism] With power and signal in the same trench, the mains-frequency magnetic field of the power cable couples into the signal cable, producing a common-mode spike every cycle.
[Calculation] With a 50mm separation in the same trench, power I=50A and B=μ0I/2πr≈2e-4T, the EMF induced in the signal loop gives a spike every 20ms cycle, with amplitude ±0.3℃.
[Design Omission] Power and signal shared the same trench, with no separate ducts and no shielding.
① Separate ducts: put power and signal in separate trenches (separation ≥300mm) or separate trays → coupling eliminated, spikes go to zero
② Shielded twisted pair: change the signal cable to shielded twisted pair → suppresses induction
③ Metal partition: add a metal partition in the same trench → shielding ≥30dB
④ Single-end grounding: ground the shield at one point → avoids ground loops
⑤ Filtering: add a 50Hz notch plus averaging to the AI → spikes pressed to ≤0.05℃
⑥ Isolation: add isolation → cuts common mode
⑦ Verify by measurement: AI spikes under same-trench conditions (≤0.05℃) → confirmed
⑧ Institutionalize: write the routing separation into the wiring diagram → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields