E45-139 · Power Supply · Pressure Transmitter · ★★
When a large motor soft-starts, the pressure transmitter in the same cabinet momentarily reads zero and recovers after 0.5s
[Mechanism] Although a soft starter limits the current, it still causes a momentary grid voltage dip; the non-isolated supply in the same cabinet dips with it, and the transmitter resets on undervoltage and reads zero.
[Calculation] Even with the soft-start current limited to 3× rated, the bus still drops 15% for 0.5s; an unisolated 24V supply dips to <12V → the transmitter resets and reads zero.
[Design Omission] The transmitter shared a bus with the motor soft starter, with no isolation and no hold-up capacitor.
① Independent isolated supply for the transmitter: use an isolated regulated supply for sensing → no dip, no zeroing
② Hold-up capacitor: add 15mF across the bus → covers the 0.5s dip without losing power
③ Separate cabinets: feed the sensing and the motor soft starter from different cabinets → no shared bus
④ PLC hold: hold the last analog value through a brief dropout → no false judgment
⑤ Soft-start ramp: lengthen the ramp time to reduce the voltage dip → less inrush
⑥ Measure the soft-start dip: sensing-end voltage under load ≥14V → confirmed
⑦ Reset verification: the reading does not zero out under soft-start conditions → confirmed
⑧ Write the isolated supply into the drawing → gate at the source
GB/T 17626.4-2018