E45-141 · Power Supply · 24V Switching Supply · ★★
The distribution cabinet is sealed, so on summer afternoons the power module shuts down periodically and instrument readings come and go
[Mechanism] A switching supply is about 85% efficient, so the remaining 15% becomes heat; with the cabinet sealed and no convection the module case temperature climbs to the over-temperature protection point (about 70℃) and it shuts down, recovering once it cools.
[Calculation] With a 100W module output, 15W of loss, no airflow in the cabinet, ΔT=P×Rθ=15×3=45℃ and 40℃ ambient → a case temperature of 85℃, above the 70℃ protection point → shutdown.
[Design Omission] The cabinet had no ventilation, the module was given no thermal margin, and there was no over-temperature warning.
① Forced cabinet ventilation: add a fan for convection, case temperature ≤55℃ → no over-temperature
② Module derating: choose a rating ≥1.5× the load → ample thermal margin
③ Thermal clearance: leave ≥50mm of air duct above and below the module → free heat flow
④ Over-temperature warning: alarm when the module temperature >60℃ → intervene early
⑤ Better natural cooling: add heat sinks on the cabinet walls → lower ΔT
⑥ Temperature-rise measurement: case temperature at full load ≤60℃ → confirmed
⑦ Redundant supply: hot-standby changeover → a shutdown does not lose the supply
⑧ Write the thermal design into the cabinet specification → gate at the source
GB/T 7260.3-2003