Knowledge Base › Electrical Sensor Error Case › Slow Output Voltage Drift Without Calibration Causes Bias

Slow Output Voltage Drift Without Calibration Causes Bias

E45-173 · Power Supply · 24V Supply · ★★

Problem Description

Yearly drift of the supply takes the output from 24V to 23.2V, biasing readings across the whole system by 1%

Root Cause

[Mechanism] Temperature drift and aging of the reference components make the output voltage fall slowly, and without calibration over time the whole system ends up biased.
[Calculation] A yearly drift of −0.8V (about −3%), reaching 23.2V, biases the reading of transmitters that depend on this voltage by about 1%; an annual calibration corrects it.
[Design Omission] The supply has no periodic calibration and no output monitoring, so the drift goes unnoticed.

Corrective Solution

① Periodic calibration: calibrate the supply output voltage annually → corrects the drift
② Output monitoring: display the voltage trend online → detect it early
③ Precise reference: select a low-drift reference supply → yearly drift <0.5%
④ Alarm: alarm when the voltage deviates >2% from rated → early warning
⑤ Margin: ≥23.5V under load → leaves margin
⑥ Voltage measurement: loaded output ≥23.5V → verify
⑦ Aging warning: replace before end of life → no sudden failure
⑧ Write the calibration interval into maintenance → gate at the source

Checklist

Reference

GB/T 7260.3-2003