E45-180 · Grounding and Shielding · Control Cabinet · ★★★
The insulation monitor reports 2mA of leakage current from the cabinet enclosure to ground, and touching the cabinet gives a tingling sensation
[Mechanism] Leakage from equipment inside the cabinet or stray-capacitance coupling puts the enclosure at a floating potential; with no PE bond a person touching the cabinet completes a circuit and the leakage current flows through the body to ground, causing the tingling; an ungrounded enclosure also leaves internal interference with no discharge path.
[Calculation] Stray capacitance C=100pF at 220V, 50Hz → capacitive leakage I=2πfCU≈6.9μA; combined with resistive leakage from poor insulation the total reaches 2mA; the safety limit is ≤3.5mA.
[Design Omission] The cabinet has no protective earth connection; the PE terminal is left empty or only loosely connected.
① Cabinet to PE: bond the cabinet to the PE bar with ≥4mm² yellow-green ground wire → forces the enclosure to the same potential
② Reliable clamping: torque the PE terminal ≥2.5N·m against loosening → firm contact
③ Equipotential bar: fit a grounding copper bar in the cabinet collecting all equipment shells → unified grounding
④ Insulation monitoring: install an insulation monitor, leakage current <3.5mA → alarms on exceedance
⑤ RCD: add a 30mA residual-current device to the supply circuit → fast trip on contact
⑥ Contact resistance test: cabinet-shell-to-PE resistance <0.1Ω → verify continuity
⑦ Periodic inspection: check the PE wire quarterly for looseness and corrosion → long-term reliability
⑧ Write protective earthing into the electrical safety specification → gate at the source
GB/T 25295-2010 Guidelines for safety design of electrical equipment