E45-218 · Grounding and Shielding · Lightning Down-Conductor · ★★
After a lightning strike the down-conductor heated and discoloured; its cross-section was too small, causing thermal damage and slow current drainage
[Mechanism] A small down-conductor cross-section means high resistance; as the lightning current drains, the I²R heating raises the conductor temperature, and a thin wire overheats, melts or damages its insulation; an undersized section also gives high drainage impedance.
[Calculation] With a lightning current I=20kA and a thin conductor of R=0.05Ω, the heat I²R=20MW raises the temperature almost instantly and overheats a 35mm² conductor; the code requires ≥50mm².
[Design Omission] An ordinary thin wire was used as the down-conductor and did not meet the lightning-protection cross-section.
① Larger cross-section: use ≥50mm² copper cable or angle steel for the down-conductor → withstands lightning heating
② Short straight path: keep the down-conductor short and straight without bends → lowers inductive reactance
③ Corrosion protection: hot-dip galvanise the down-conductor → no rust-through
④ Separate routing: keep the down-conductor away from equipment cables → less coupling
⑤ Solid joints: weld or crimp the joints → low resistance
⑥ Temperature check: after a strike, no overheating or discolouration → confirmed
⑦ Section check: size the cross-section by lightning-current level → satisfied
⑧ Write the down-conductor specification into the lightning-protection design → control at the source
GB 50057-2010 Design code for protection of structures against lightning