Knowledge Base › Electrical Sensor Error Case › Shield Miswired to Signal Ground Causing Ground Loop Current

Shield Miswired to Signal Ground Causing Ground Loop Current

E45-231 · Wiring and Terminals · Analog Shielded Cable · ★

Problem Description

The cable shield was tied to signal ground instead of chassis ground, so the 4-20mA reading carried ±1% mains-frequency ripple

Root Cause

[Mechanism] The shield should be grounded to earth or the chassis to drain interference; wired by mistake to signal ground it shares a node with the signal return and forms a ground-loop path, and mains-frequency interference is injected through the shield into signal ground as common-mode ripple.
[Calculation] A 1V potential difference between the two grounds drives a 2A loop current through the shield resistance R=0.5Ω, inducing a ±0.2% mains-frequency component across the signal-source impedance and making the reading jitter.
[Design Omission] The shield-grounding rule was unclear, signal ground and protective ground were tied together, and single-point grounding was not used.

Corrective Solution

① Shield to chassis: tie the shield to chassis/earth → drains interference
② Single-point ground: ground the shield at one end only, not to signal ground → breaks the loop
③ Clear rule: document a shield-grounding diagram → follow it
④ Ripple check: measure signal ripple <0.5% → confirmed
⑤ Ground isolation: isolate signal ground from earth → no mixing
⑥ Both-end check: verify only one end is bonded to chassis → loop stays broken
⑦ Mains test: the reading is stable with no 50Hz component → confirmed
⑧ Write shield grounding into the process → control at the source

Checklist

Reference

GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields