E45-367 · Environmental Protection and Temperature/Humidity · Pressure Transmitter · ★★
In a basement pump room with long-term high humidity, the insulation in the pressure transmitter's terminal chamber ages and absorbs moisture year after year, raising the leakage current and shifting the zero point
[Mechanism] Long-term high humidity makes the insulating material absorb moisture, increasing dielectric loss and accelerating aging; the leakage current introduces a zero offset.
[Calculation] With the pump room at 95%RH year-round, moisture adsorbed by the insulation raises the leakage current from the μA level to 50μA, introducing a 0.6%FS zero drift.
[Design Deficiency] The terminal chamber had no moisture-proof measures and no drying breather.
① Sealed moisture protection: choose an IP67 terminal chamber and add seals → keep out moisture
② Potting for moisture isolation: epoxy-pot the terminal chamber → eliminate moisture ingress
③ Drying breather: add a moisture-proof breather with desiccant → control internal humidity
④ Slight heating to remove moisture: keep the cavity above the dew point → suppress moisture absorption
⑤ Moisture-resistant insulation: choose high-insulation, moisture-resistant terminals → reduce drift
⑥ Regular testing: track the trend of insulation resistance → early detection
⑦ Damp-heat verification: run a cyclic damp heat test to confirm → data confirmation
⑧ Selection standardization: write the high-humidity condition into the moisture-proof selection criteria → control at the source
GB/T 2423.4-2008 Environmental testing for electric and electronic products - Damp heat, cyclic test