Ordinary, non-real-time Ethernet used for control has large message latency jitter, causing motion control to lose synchronization
[Mechanism] CSMA/CD contention and queuing on ordinary Ethernet make message latency indeterminate; jitter beyond the control cycle causes loss of synchronization.
[Calculation] Latency jitter of ±5 ms through an ordinary switch exceeds the 1 ms control cycle; multi-axis synchronization error exceeds tolerance.
[Design Deficiency] Real-time control did not use real-time Ethernet.
① Real-time network: use real-time Ethernet IRT for control → deterministic timing
② Priority: set VLAN priority QoS → protect control frames
③ Separate segment: physically isolate the control network from the office network → no contention
④ Jitter budgeting: latency jitter ≤ control cycle → keep synchronization
⑤ Load control: leave margin in control-network load → stable latency
⑥ Jitter monitoring: monitor latency jitter and alarm → early detection
⑦ Jitter verification: measure end-to-end jitter → data confirmation
⑧ Selection standardization: write real-time requirements into the networking spec → control at the source
GB/T 30094-2013 Technical specification for industrial Ethernet switches