E45-423 · Communication and Bus · Communication Module · ★★
The communication shield or communication ground is grounded at several points, forming a loop; the circulating current induces noise and causes communication bit errors
[Mechanism] The potential difference between multiple grounding points drives a circulating current, and the circulating current generates longitudinal noise in the shield that couples into the signal.
[Calculation] A 5 V potential difference between two ground points forms a circulating current in the shield; the induced noise exceeds the tolerance and causes bit errors.
[Design Deficiency] The shield was grounded at several points instead of a single point.
① Single-point grounding: ground the shield and communication ground at one point only → break the loop
② Floating layout: leave remote devices floating, not grounded → avoid loops
③ Isolated transceivers: use isolated transceivers to break ground coupling → resist circulating current
④ Equipotential bonding: bond the two points to lower the potential difference
⑤ Grounding review: check for multi-point grounding at completion and correct it to single-point → early correction
⑥ Loop-current monitoring: measure shield current and alarm → early detection
⑦ Loop verification: measure circulating current and bit errors → data confirmation
⑧ Selection standardization: write single-point grounding into the grounding spec → control at the source
GB/T 50065-2011 Code for design of grounding for AC electrical installations