E45-449 · Vibration and Mechanical Stress · Temperature Sensor · ★★
Vibration loosens the thermocouple measuring junction; the contact thermal resistance rises and the temperature reading is low and fluctuating
[Mechanism] Vibration makes the junction micro-move and oxidize; the contact resistance and thermal resistance rise, making the measured temperature low and unstable.
[Calculation] A loose junction raises the contact thermal resistance, making the measuring point read 5℃ low and fluctuate.
[Design Deficiency] The junction was not welded and relied only on crimping.
① Welded fixing: laser or argon-arc weld the junction → stabilize contact
② Sheathed protection: use a sheathed thermocouple for vibration resistance → protect the junction
③ Clamping lock: add a lock at the crimp → prevent movement
④ Insulation: insulate the junction to prevent short circuits → ensure accuracy
⑤ Regular check: inspect the junction for integrity → early correction
⑥ Temperature monitoring: alarm on temperature fluctuation → early detection
⑦ Loosening verification: confirm by measuring temperature under vibration → data confirmation
⑧ Selection standardization: write junction fixing into the assembly spec → control at the source
GB/T 16839.1-1997 Thermocouples - Part 1: Reference tables