Flange gaskets are chosen by pressure-temperature class (PN / Class): (1) non-metallic — asbestos / non-asbestos rubber sheet, PTFE, for low pressure and medium temperature (2.5 MPa and below, 200 C and below); (2) semi-metallic — spiral-wound gasket (metal strip + flexible graphite), general for medium-high pressure and high temperature, with inner and outer rings to prevent extrusion; (3) metallic — serrated gasket, metal ring (octagonal / oval), for high pressure and high temperature (e.g. valves, reactors). Selection: by flange standard (HG / GB / ANSI) choose the sealing face (FF / RF / RTJ) and gasket model; bolts should be tightened symmetrically and evenly to the specified torque; graphite gaskets avoid strong oxidation and radiation. Leakage is mostly from uneven torque or a crushed gasket. For maintenance see g-01. (Note: statistics show about 80% of leakage comes from assembly cleanliness and uneven torque, not the seal itself. Assembly should be done on a clean bench, with shaft / bore deburred and chamfered and a guide sleeve to avoid cutting the ring; tighten bolts symmetrically and crosswise to the specified torque. On commissioning, run in at low pressure first then raise it; if seepage appears, check the torque before replacing parts.)