Vibration isolation, at its core, answers one question: to what fraction of the excitation frequency must the equipment's natural frequency be pushed?
Yet the most common real-project scenario is this — drop the fan on the floor slab, the client says there is vibration felt below, you buy four rubber pads off the web and stuff them in; a little effect but not much; swap in four springs and it sways badly and 'clanks' into the stop on start-up. The real reason is not a bad isolator choice but that you never calculated the frequency ratio.
Below we calculate through a rooftop centrifugal fan from scratch: first set the frequency ratio, then back-calculate stiffness and static deflection, finally check start-up resonance and single-support load.
11 kW centrifugal fan unit (including motor, belt guard, common base), mounted on the office-building roof concrete slab; offices below.
| Parameter | Symbol | Value |
|---|---|---|
| Total unit mass (with base) | m | 480 kg |
| Fan speed | n | 1450 r/min |
| Impeller + spindle mass | mr | 85 kg |
| Rotor balance grade (ISO 1940) | G6.3 | — |
| Number of isolators | N | 4 pieces, evenly at the four base corners |
| Isolator material | — | Natural rubber-steel composite (ζ≈0.06) |
| Acceptance requirement | T | Transmissibility ≤ 0.10 (isolation efficiency ≥ 90%) |
Note: here only the rotational frequency is taken as the main excitation. A 1450 r/min fan's blade-pass frequency reaches several hundred Hz — that is aeroacoustic noise and thin-plate secondary radiation, not solvable by isolators; separate acoustic treatment is needed.
Rotational frequency:
This is the target 'enemy frequency' of isolation design. All natural frequencies must be pushed down around it.
Take the damping ratio for rubber-metal composite as ζ = 0.06. Transmissibility formula:
Trial calculations at different frequency ratios r:
| Frequency ratio r | 2.0 | 2.5 | 3.0 | 3.4 | 3.5 | 4.0 |
|---|---|---|---|---|---|---|
| Transmissibility T | 0.342 | 0.199 | 0.133 | 0.102 | 0.096 | 0.074 |
| Isolation efficiency η | 65.8% | 80.1% | 86.7% | 89.8% | 90.4% | 92.6% |
Solving T = 0.10 gives the critical value r = 3.44. Allow some engineering margin, take r = 3.5, giving T = 0.0962, η = 90.4%, meeting the target.
This column is the most worth remembering: at r = 2.0 isolation efficiency is only 66%, at r = 3.0 it is 87%, and only at r = 3.5 does it just reach 90%. The so-called 'isolators installed, so it works' effect most likely stalls at the r = 2 level.
Natural frequency:
Single-DOF system k = m·(2πfn)², note rad/s here:
Four evenly distributed, single-support stiffness: 902 / 4 = 225.5 N/mm。
These are the two hard criteria for selection: individual vertical stiffness ≈ 226 N/mm, system natural frequency 6.9 Hz. Taking these two numbers to look up an isolator catalog is far more reliable than saying 'which one for an 11 kW fan'.
Static deflection δ = mg / k:
The simplified formula gives the same result: δ = 248.5 / fn² = 248.5 / 47.61 = 5.22 mm。
This 5.22 mm determines two things: first, the isolator must have a static compression of ≥ 5.2 mm (if the rubber pad cannot reach this amount, the stiffness cannot drop); second, the installation space below the base must be no less than 12–15 mm, leaving a margin for static plus dynamic deflection. Many sites find it 'useless after installation' simply because the rubber pad is only 10 mm thick and bottoms out at 2 mm, so the actual stiffness is two to three times the design value, fn goes straight up, r drops to around 1.5 — amplification, not isolation.
First calculate the allowable eccentricity per balance grade G6.3. The meaning of G6.3 is eper·ω = 6.3 mm/s:
Rotor residual unbalance U = mr·eper = 85 × 0.0415 = 3.53 kg·mm, centrifugal excitation force:
Damped steady-state amplitude A = (F₀/k) / √[(1 − r²)² + (2ζr)²]:
Equivalent vibration velocity v = 2πf·A = 2π × 24.17 × 0.0080 = 1.21 mm/s, falling in the 'good' range of ISO 10816 (< 2.8 mm/s). Force transmitted to the floor Ft = T·F₀ = 0.0962 × 81.3 = 7.8 N, an order of magnitude lower than the 81.3 N under rigid mounting.
Startup resonance check:The fan, ramping from 0 to 24.17 Hz, must sweep through fn = 6.9 Hz. At this point β = 1, amplitude amplification factor = 1/(2ζ) = 1/0.12 = 8.33:
With an additional dynamic deflection of 0.75 mm plus the static deflection of 5.22 mm, the maximum deformation of a single isolator is about 6 mm; rubber isolators allow 10–15 mm, so it is safe. But with a coil spring (ζ ≈ 0.001, 500× amplification), this figure reaches over 45 mm and damping or a stop must be added — this is the arithmetic behind 'swap to a spring and it hits the stop'.
Single-unit load capacity:
Accounting for a load-imbalance factor of 1.2 for center-of-gravity eccentricity and belt tension, select each isolator for 144 kg. Choose an isolator rated load ≥ 150 kg, vertical stiffness 226 N/mm, allowable deformation ≥ 8 mm.
Final conclusion:Select 4 natural-rubber/steel composite isolators, rated load class 150 kg, vertical stiffness 225 N/mm, system fn = 6.9 Hz, r = 3.5, T = 0.096, η = 90.4%, meets the target. At installation, level the four corners, tighten then back off half a turn; the isolators must not be subjected to shear preload.
In the transmissibility formula, r = f/fn — this ratio divides the entire isolation design into three segments:
| Region | Frequency ratio r | Behavior of T | Engineering implication |
|---|---|---|---|
| Stiffness zone (quasi-static) | r < 0.5 | T ≈ 1, slightly greater than 1 | The isolator is equivalent to a rigid body — installed for nothing |
| Resonance region | 0.8 < r < 1.2 | T reaches its peak of 1/(2ζ) | Amplitude amplified 8–20×; must be avoided |
| Transition region | 1.2 ≤ r < √2≈1.41 | T drops from peak to 1 | Still amplifying; not acceptable for delivery |
| Isolation region | r > √2 | T < 1, decreases monotonically with r | Genuinely effective; engineering practice takes r ≥ 2.5 |
r = √2 = 1.414 is the 'onset line' of isolation, where T is exactly 1. Below it, installing an isolator is worse than not. Many people don't know this line, leading to projects that 'dare to deliver at a frequency ratio of 1.3'.
Force transmissibility Tf = Ft/F₀ and the displacement transmissibility (ratio of the equipment's absolute displacement response under base excitation) Td = X/Y; under the assumptions of single-degree-of-freedom, linear, and sufficiently rigid base, the expressions are identical — both are the damped formula above. But when using them, see clearly what the input is:
Look at the formula: the damping term (2ζr)² appears in both numerator and denominator. When r is large, both are dominated by it, so T approaches a lower limit:
At ζ = 0.06 the isolation efficiency ceiling is 94%; at ζ = 0.15 (polyurethane) the ceiling is only 85%, which no amount of added stiffness can push down. Conversely, the larger ζ is, the lower the resonance peak (peak = 1/(2ζ)), and the safer startup is.
So the logic for material selection is:For ultimate isolation efficiency choose low damping (metal spring ζ≈0.001, but add a separate damper); for smooth startup and shock resistance choose high damping (rubber / polyurethane, at the cost of a lower efficiency ceiling).You cannot have both unless you use two-stage isolation or add an independent viscous damper.
This is the most practically useful formula on site. For 5 Hz you need a static deflection of 9.9 mm; for 3 Hz you need 27.6 mm. No isolator pad only 15 mm thick can give you 3 Hz — that is impossible, and you would have to go to an air spring.
Use Pa for E, m⁴ for I, m for L, and kg for m. In practice use it to judge 'whether the equipment itself is stiff enough'; if the equipment's own first-mode frequency is only 20 Hz with a 24 Hz excitation, even the best isolator is useless — the machine frame resonates first.
Note that the (2ζr)² term in the denominator cannot be omitted. Omitting it (the 'undamped approximation') yields infinity near r = 1 and underestimates the amplitude by about 0.3% at r = 3.5 — the error is small, but near the resonance point it is completely wrong, and using it to check the startup process leads to incorrect conclusions.
| Symbol | Meaning | Unit | Value notes |
|---|---|---|---|
| m | Total mass of isolation system | kg | Equipment + base + accessories, excluding foundation |
| k | Total stiffness of isolators | N/m | For multiple units in parallel, simply add them |
| f | Excitation frequency | Hz | Speed/60; for reciprocating machinery use 2× (two impacts per revolution) |
| fn | System natural frequency | Hz | Vertical dominant; lateral calculated separately |
| r | Frequency ratio | — | f/fn, engineering takes 2.5–5 |
| ζ | Damping ratio | — | Steel 0.001–0.003, cast iron 0.003, rubber 0.05–0.15 |
| T | Transmissibility | — | ≤0.1 for conventional acceptance, ≤0.05 for precision equipment |
| δ | Static deflection | mm | mg/k, determines installation space |
| Type | ζ | Attainable fn | Applications | Note |
|---|---|---|---|---|
| Rubber pad (flat) | 0.05~0.10 | 15~30 Hz | Small pumps, fans, precision instruments | Small static deflection; prone to 'short-circuit' at high frequency |
| Rubber–metal composite | 0.06~0.15 | 8~15 Hz | General fans, pumps, HVAC units | Best cost-performance; first choice |
| Helical steel spring | 0.001~0.005 | 2~8 Hz | Large-mass equipment, low-frequency requirements | Must add damping/stops, otherwise it hits the stop at startup |
| Air spring | 0.03~0.08 | 0.7~3 Hz | Precision equipment, over-subway decks, test rigs | Requires air supply, high cost, needs leveling |
| Wire rope / metal rubber | 0.10~0.20 | 5~15 Hz | High temperature, oil, corrosive environments | Good shock resistance; efficiency ceiling limited by damping |
| Cork / felt | 0.06~0.10 | 25~40 Hz | Simple isolation for building equipment | Only for high frequency; don't expect low frequency |
| Item | Recommended practice | Reason |
|---|---|---|
| Number of isolators | Multiple of 4, minimum 4 units | Three-point support is unstable; vibrating machines tend to sway |
| Center-of-gravity position | Must fall within the geometric centroid of the four isolators, with deviation ≤ 10% of the side length | Otherwise individual isolators overload, deflections become inconsistent, and sway modes appear |
| Load-imbalance factor | 1.2–1.5 (belt drive takes 1.5) | Belt tension, duct reaction, center-of-gravity estimation error |
| Lateral stiffness | Not less than 0.3× the vertical stiffness | Fans have lateral excitation; too-soft lateral stiffness causes swaying |
| Difference between natural frequency and rotational speed | fn ≤ 0.3f, and avoid 0.85f–1.15f | Account for speed fluctuation and grid frequency variation |
| Equipment | Speed r/min | Excitation f | Target fn | Corresponding r |
|---|---|---|---|---|
| Small ventilation fan | 2900 | 48.3 Hz | 10~12 Hz | 4~5 |
| Centrifugal fan | 1450 | 24.2 Hz | 6~7 Hz | 3.5~4 |
| Centrifugal water pump | 1450 | 24.2 Hz | 6~7 Hz | 3.5~4 |
| Chiller unit | 1450 | 24.2 Hz | 6~8 Hz | 3~4 |
| Punch press (impact type) | — | By stroke count × 2 | 3~5 Hz | — |
| Precision instrument table | — | Foundation 1–80 Hz | 1.5~3 Hz | — |
Impact-type equipment (punch presses, forging hammers, vibrating screens) cannot be evaluated by steady-state transmissibility alone; you must compute deformation energy from impulse and also consider the combination of the foundation mass block (inertia block) with the isolators, otherwise the peak force cannot be determined. Such equipment generally requires an inertia block mass ≥ 1–2× the equipment mass.
| Wrong practice | Consequence | Correct approach |
|---|---|---|
| Selecting isolators by equipment power or 'which model' instead of by mass | fn offset, r falls into the 1.2–1.5 amplification zone — worse than not installing | First compute m, then set fn, then compute k, and finally look up the catalog by k and load |
| Taking a frequency ratio of 2.0–2.5 as 'good enough' | T = 0.20–0.34, isolation efficiency only 66%–80%; the client can still feel the vibration | For conventional acceptance take r ≥ 3.5; for precision equipment take r ≥ 4.5 |
| Ignoring the physical lower limit of static deflection | The rubber pad cannot be compressed; actual stiffness far exceeds the nominal, fn rises by 1.5–2× | First compute static deflection by δ = 248.5/fn², then check the isolator thickness and allowable compression |
| Coil spring without damping or stops | During startup frequency sweep, amplitude amplifies 500×; the isolator bottoms out and the base hits the foundation | Add a viscous damper or built-in friction damping, fit stop blocks, and leave a gap of 1.5× the resonance amplitude |
| Distributing load equally to four corners without accounting for center-of-gravity eccentricity and belt tension | Individual isolators overload by over 30%, deflections become inconsistent, and the unit tilts and drifts | Distribute load by actual center of gravity, with a load-imbalance factor of 1.2–1.5, and increase stiffness on one side if necessary |
| Using high-damping material to pursue high efficiency | At ζ = 0.15 the efficiency ceiling is only 85%; no stiffness change can break through it | First recognize that Tmin ≈ 2ζ ceiling; for higher efficiency switch to low damping + independent damper |
| Using isolators to treat high-frequency noise | Above 1 kHz the rubber 'short-circuits' internally and the isolator becomes a sound bridge | Isolation solves structural vibration of 5–100 Hz; high frequency relies on acoustic enclosures, damping coatings, and floating floors |
One final piece of field experience: after installing an isolation system, always perform a startup frequency sweep or at least observe the startup process. If there is obvious swaying or metallic banging at the instant of startup, or if the few seconds of 'passing through resonance' during shutdown sway ten times worse than during operation, you can basically conclude that the damping is insufficient or the stop clearance is wrong — at that point changing stiffness is useless; you must change the damping structure.
The real difficulty in isolation design has never been the formulas, but getting 'mass, speed, center of gravity' right on site. Once these three are pinned down, all that remains is plugging in the frequency ratio of 3.5.