Knowledge Base › General calculations and examples › How to cure fan vibration transmitted to the floor? Vibration-isolation design example

How to cure fan vibration transmitted to the floor? Vibration-isolation design example

🛠️ Baisi Technical Handbook · 500+ standard parts intelligent selection calculations
Covering pneumatic/motor/transmission/reducer/coupling/bearing/hydraulic/pneumatic/screw/worm/spring full series
Avoid 95% of design errors, improve efficiency by 80%
Master 10 years of senior engineer experience in 3 months
Download link: https://pan.baidu.com/s/1bquayZpfas6oYBbG0gp3Gw?pwd=2giv

📖 Coming up next: Surface roughness selection

Vibration isolation, at its core, answers one question: to what fraction of the excitation frequency must the equipment's natural frequency be pushed?

Yet the most common real-project scenario is this — drop the fan on the floor slab, the client says there is vibration felt below, you buy four rubber pads off the web and stuff them in; a little effect but not much; swap in four springs and it sways badly and 'clanks' into the stop on start-up. The real reason is not a bad isolator choice but that you never calculated the frequency ratio.

Below we calculate through a rooftop centrifugal fan from scratch: first set the frequency ratio, then back-calculate stiffness and static deflection, finally check start-up resonance and single-support load.

I. Complete Calculation Example

Step 1 | Lay out the duty parameters

11 kW centrifugal fan unit (including motor, belt guard, common base), mounted on the office-building roof concrete slab; offices below.

ParameterSymbolValue
Total unit mass (with base)m480 kg
Fan speedn1450 r/min
Impeller + spindle massmr85 kg
Rotor balance grade (ISO 1940)G6.3—
Number of isolatorsN4 pieces, evenly at the four base corners
Isolator material—Natural rubber-steel composite (ζ≈0.06)
Acceptance requirementTTransmissibility ≤ 0.10 (isolation efficiency ≥ 90%)

Note: here only the rotational frequency is taken as the main excitation. A 1450 r/min fan's blade-pass frequency reaches several hundred Hz — that is aeroacoustic noise and thin-plate secondary radiation, not solvable by isolators; separate acoustic treatment is needed.

Step 2 | Calculate the excitation frequency

Rotational frequency:

f = n / 60 = 1450 / 60 = 24.17 Hz

This is the target 'enemy frequency' of isolation design. All natural frequencies must be pushed down around it.

Step 3 | Back-calculate the frequency ratio from the transmissibility requirement

Take the damping ratio for rubber-metal composite as ζ = 0.06. Transmissibility formula:

T = √[ (1 + (2ζr)²) / ((1 − r²)² + (2ζr)²) ]

Trial calculations at different frequency ratios r:

Frequency ratio r2.02.53.03.43.54.0
Transmissibility T0.3420.1990.1330.1020.0960.074
Isolation efficiency η65.8%80.1%86.7%89.8%90.4%92.6%

Solving T = 0.10 gives the critical value r = 3.44. Allow some engineering margin, take r = 3.5, giving T = 0.0962, η = 90.4%, meeting the target.

This column is the most worth remembering: at r = 2.0 isolation efficiency is only 66%, at r = 3.0 it is 87%, and only at r = 3.5 does it just reach 90%. The so-called 'isolators installed, so it works' effect most likely stalls at the r = 2 level.

Step 4 | Determine the natural frequency and required total stiffness

Natural frequency:

fn = f / r = 24.17 / 3.5 = 6.9 Hz

Single-DOF system k = m·(2πfn)², note rad/s here:

k = 480 × (2π × 6.9)² = 480 × 1879.5 = 902 160 N/m = 902 N/mm

Four evenly distributed, single-support stiffness: 902 / 4 = 225.5 N/mm。

These are the two hard criteria for selection: individual vertical stiffness ≈ 226 N/mm, system natural frequency 6.9 Hz. Taking these two numbers to look up an isolator catalog is far more reliable than saying 'which one for an 11 kW fan'.

Step 5 | Calculate Static Deflection and Verify Installation Height

Static deflection δ = mg / k:

δ = 480 × 9.81 / 902 160 = 0.00522 m = 5.22 mm

The simplified formula gives the same result: δ = 248.5 / fn² = 248.5 / 47.61 = 5.22 mm。

This 5.22 mm determines two things: first, the isolator must have a static compression of ≥ 5.2 mm (if the rubber pad cannot reach this amount, the stiffness cannot drop); second, the installation space below the base must be no less than 12–15 mm, leaving a margin for static plus dynamic deflection. Many sites find it 'useless after installation' simply because the rubber pad is only 10 mm thick and bottoms out at 2 mm, so the actual stiffness is two to three times the design value, fn goes straight up, r drops to around 1.5 — amplification, not isolation.

Step 6 | Calculate Excitation Force and Vibration Amplitude

First calculate the allowable eccentricity per balance grade G6.3. The meaning of G6.3 is eper·ω = 6.3 mm/s:

ω = 2π × 24.17 = 151.9 rad/s
eper = 6.3 / 151.9 = 0.0415 mm = 41.5 μm

Rotor residual unbalance U = mr·eper = 85 × 0.0415 = 3.53 kg·mm, centrifugal excitation force:

F₀ = U·ω² = 3.53×10⁻³ × 151.9² = 81.3 N

Damped steady-state amplitude A = (F₀/k) / √[(1 − r²)² + (2ζr)²]:

F₀/k = 81.3 / 902 = 0.0901 mm
A = 0.0901 / 11.27 = 0.0080 mm = 8.0 μm

Equivalent vibration velocity v = 2πf·A = 2π × 24.17 × 0.0080 = 1.21 mm/s, falling in the 'good' range of ISO 10816 (< 2.8 mm/s). Force transmitted to the floor Ft = T·F₀ = 0.0962 × 81.3 = 7.8 N, an order of magnitude lower than the 81.3 N under rigid mounting.

Step 7 | Check Startup Resonance and Individual Load Capacity

Startup resonance check:The fan, ramping from 0 to 24.17 Hz, must sweep through fn = 6.9 Hz. At this point β = 1, amplitude amplification factor = 1/(2ζ) = 1/0.12 = 8.33:

Ares = (F₀/k) / (2ζ) = 0.0901 / 0.12 = 0.75 mm

With an additional dynamic deflection of 0.75 mm plus the static deflection of 5.22 mm, the maximum deformation of a single isolator is about 6 mm; rubber isolators allow 10–15 mm, so it is safe. But with a coil spring (ζ ≈ 0.001, 500× amplification), this figure reaches over 45 mm and damping or a stop must be added — this is the arithmetic behind 'swap to a spring and it hits the stop'.

Single-unit load capacity:

Static load = 480 × 9.81 / 4 = 1177 N = 120 kg

Accounting for a load-imbalance factor of 1.2 for center-of-gravity eccentricity and belt tension, select each isolator for 144 kg. Choose an isolator rated load ≥ 150 kg, vertical stiffness 226 N/mm, allowable deformation ≥ 8 mm.

Final conclusion:Select 4 natural-rubber/steel composite isolators, rated load class 150 kg, vertical stiffness 225 N/mm, system fn = 6.9 Hz, r = 3.5, T = 0.096, η = 90.4%, meets the target. At installation, level the four corners, tighten then back off half a turn; the isolators must not be subjected to shear preload.

🛠️ Baishi Technical Manual · One-click isolator parameter results
Baisi Technical Handbook has integrated this calculation module into Batch 3 Professional In-Depth Calculation Module. Enter the operating parameters and it automatically outputs the selection result. No more manual lookups, no more hand calculations, no more experience-based estimates.—— Baisi Technical Handbook download link https://pan.baidu.com/s/1bquayZpfas6oYBbG0gp3Gw?pwd=2giv

II. The Three Isolation Zones — Know Them Before You Start

In the transmissibility formula, r = f/fn — this ratio divides the entire isolation design into three segments:

RegionFrequency ratio rBehavior of TEngineering implication
Stiffness zone (quasi-static)r < 0.5T ≈ 1, slightly greater than 1The isolator is equivalent to a rigid body — installed for nothing
Resonance region0.8 < r < 1.2T reaches its peak of 1/(2ζ)Amplitude amplified 8–20×; must be avoided
Transition region1.2 ≤ r < √2≈1.41T drops from peak to 1Still amplifying; not acceptable for delivery
Isolation regionr > √2T < 1, decreases monotonically with rGenuinely effective; engineering practice takes r ≥ 2.5

r = √2 = 1.414 is the 'onset line' of isolation, where T is exactly 1. Below it, installing an isolator is worse than not. Many people don't know this line, leading to projects that 'dare to deliver at a frequency ratio of 1.3'.

Don't mix up the two kinds of transmissibility

Force transmissibility Tf = Ft/F₀ and the displacement transmissibility (ratio of the equipment's absolute displacement response under base excitation) Td = X/Y; under the assumptions of single-degree-of-freedom, linear, and sufficiently rigid base, the expressions are identical — both are the damped formula above. But when using them, see clearly what the input is:

Damping is a double-edged sword

Look at the formula: the damping term (2ζr)² appears in both numerator and denominator. When r is large, both are dominated by it, so T approaches a lower limit:

As r → ∞, Tmin ≈ 2ζ

At ζ = 0.06 the isolation efficiency ceiling is 94%; at ζ = 0.15 (polyurethane) the ceiling is only 85%, which no amount of added stiffness can push down. Conversely, the larger ζ is, the lower the resonance peak (peak = 1/(2ζ)), and the safer startup is.

So the logic for material selection is:For ultimate isolation efficiency choose low damping (metal spring ζ≈0.001, but add a separate damper); for smooth startup and shock resistance choose high damping (rubber / polyurethane, at the cost of a lower efficiency ceiling).You cannot have both unless you use two-stage isolation or add an independent viscous damper.

III. Quick Reference of Core Formulas

1. Natural Frequency (single-DOF spring–mass)

fn = (1/2π)·√(k/m) (Hz, k in N/m)

2. Static Deflection vs. Natural Frequency Trade-off

fn ≈ 4.98 / √δ  δ = 248.5 / fn²  (mm)

This is the most practically useful formula on site. For 5 Hz you need a static deflection of 9.9 mm; for 3 Hz you need 27.6 mm. No isolator pad only 15 mm thick can give you 3 Hz — that is impossible, and you would have to go to an air spring.

3. Natural Frequency of Beam Structures (first-order approximation)

Cantilever beam with end concentrated mass: fn = (1/2π)·√(3EI / mL³)
Simply supported beam with midspan concentrated mass: fn = (1/2π)·√(48EI / mL³)

Use Pa for E, m⁴ for I, m for L, and kg for m. In practice use it to judge 'whether the equipment itself is stiff enough'; if the equipment's own first-mode frequency is only 20 Hz with a 24 Hz excitation, even the best isolator is useless — the machine frame resonates first.

4. Transmissibility and Isolation Efficiency

T = √[(1 + (2ζr)²) / ((1 − r²)² + (2ζr)²)]
η = (1 − T) × 100%

5. Damped Steady-State Amplitude

A = (F₀/k) / √[(1 − r²)² + (2ζr)²]

Note that the (2ζr)² term in the denominator cannot be omitted. Omitting it (the 'undamped approximation') yields infinity near r = 1 and underestimates the amplitude by about 0.3% at r = 3.5 — the error is small, but near the resonance point it is completely wrong, and using it to check the startup process leads to incorrect conclusions.

6. Parameter Quick-Reference Table

SymbolMeaningUnitValue notes
mTotal mass of isolation systemkgEquipment + base + accessories, excluding foundation
kTotal stiffness of isolatorsN/mFor multiple units in parallel, simply add them
fExcitation frequencyHzSpeed/60; for reciprocating machinery use 2× (two impacts per revolution)
fnSystem natural frequencyHzVertical dominant; lateral calculated separately
rFrequency ratio—f/fn, engineering takes 2.5–5
ζDamping ratio—Steel 0.001–0.003, cast iron 0.003, rubber 0.05–0.15
TTransmissibility—≤0.1 for conventional acceptance, ≤0.05 for precision equipment
δStatic deflectionmmmg/k, determines installation space

IV. Parameter Selection Guide

Isolator Type and Achievable Natural Frequency

TypeζAttainable fnApplicationsNote
Rubber pad (flat)0.05~0.1015~30 HzSmall pumps, fans, precision instrumentsSmall static deflection; prone to 'short-circuit' at high frequency
Rubber–metal composite0.06~0.158~15 HzGeneral fans, pumps, HVAC unitsBest cost-performance; first choice
Helical steel spring0.001~0.0052~8 HzLarge-mass equipment, low-frequency requirementsMust add damping/stops, otherwise it hits the stop at startup
Air spring0.03~0.080.7~3 HzPrecision equipment, over-subway decks, test rigsRequires air supply, high cost, needs leveling
Wire rope / metal rubber0.10~0.205~15 HzHigh temperature, oil, corrosive environmentsGood shock resistance; efficiency ceiling limited by damping
Cork / felt0.06~0.1025~40 HzSimple isolation for building equipmentOnly for high frequency; don't expect low frequency

Mass Distribution and Count

ItemRecommended practiceReason
Number of isolatorsMultiple of 4, minimum 4 unitsThree-point support is unstable; vibrating machines tend to sway
Center-of-gravity positionMust fall within the geometric centroid of the four isolators, with deviation ≤ 10% of the side lengthOtherwise individual isolators overload, deflections become inconsistent, and sway modes appear
Load-imbalance factor1.2–1.5 (belt drive takes 1.5)Belt tension, duct reaction, center-of-gravity estimation error
Lateral stiffnessNot less than 0.3× the vertical stiffnessFans have lateral excitation; too-soft lateral stiffness causes swaying
Difference between natural frequency and rotational speedfn ≤ 0.3f, and avoid 0.85f–1.15fAccount for speed fluctuation and grid frequency variation

Empirical Natural-Frequency Targets for Common Equipment

EquipmentSpeed r/minExcitation fTarget fnCorresponding r
Small ventilation fan290048.3 Hz10~12 Hz4~5
Centrifugal fan145024.2 Hz6~7 Hz3.5~4
Centrifugal water pump145024.2 Hz6~7 Hz3.5~4
Chiller unit145024.2 Hz6~8 Hz3~4
Punch press (impact type)—By stroke count × 23~5 Hz—
Precision instrument table—Foundation 1–80 Hz1.5~3 Hz—

Impact-type equipment (punch presses, forging hammers, vibrating screens) cannot be evaluated by steady-state transmissibility alone; you must compute deformation energy from impulse and also consider the combination of the foundation mass block (inertia block) with the isolators, otherwise the peak force cannot be determined. Such equipment generally requires an inertia block mass ≥ 1–2× the equipment mass.

V. Common Errors and Pitfalls

Wrong practiceConsequenceCorrect approach
Selecting isolators by equipment power or 'which model' instead of by massfn offset, r falls into the 1.2–1.5 amplification zone — worse than not installingFirst compute m, then set fn, then compute k, and finally look up the catalog by k and load
Taking a frequency ratio of 2.0–2.5 as 'good enough'T = 0.20–0.34, isolation efficiency only 66%–80%; the client can still feel the vibrationFor conventional acceptance take r ≥ 3.5; for precision equipment take r ≥ 4.5
Ignoring the physical lower limit of static deflectionThe rubber pad cannot be compressed; actual stiffness far exceeds the nominal, fn rises by 1.5–2×First compute static deflection by δ = 248.5/fn², then check the isolator thickness and allowable compression
Coil spring without damping or stopsDuring startup frequency sweep, amplitude amplifies 500×; the isolator bottoms out and the base hits the foundationAdd a viscous damper or built-in friction damping, fit stop blocks, and leave a gap of 1.5× the resonance amplitude
Distributing load equally to four corners without accounting for center-of-gravity eccentricity and belt tensionIndividual isolators overload by over 30%, deflections become inconsistent, and the unit tilts and driftsDistribute load by actual center of gravity, with a load-imbalance factor of 1.2–1.5, and increase stiffness on one side if necessary
Using high-damping material to pursue high efficiencyAt ζ = 0.15 the efficiency ceiling is only 85%; no stiffness change can break through itFirst recognize that Tmin ≈ 2ζ ceiling; for higher efficiency switch to low damping + independent damper
Using isolators to treat high-frequency noiseAbove 1 kHz the rubber 'short-circuits' internally and the isolator becomes a sound bridgeIsolation solves structural vibration of 5–100 Hz; high frequency relies on acoustic enclosures, damping coatings, and floating floors

One final piece of field experience: after installing an isolation system, always perform a startup frequency sweep or at least observe the startup process. If there is obvious swaying or metallic banging at the instant of startup, or if the few seconds of 'passing through resonance' during shutdown sway ten times worse than during operation, you can basically conclude that the damping is insufficient or the stop clearance is wrong — at that point changing stiffness is useless; you must change the damping structure.

The real difficulty in isolation design has never been the formulas, but getting 'mass, speed, center of gravity' right on site. Once these three are pinned down, all that remains is plugging in the frequency ratio of 3.5.

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »