E41-065 · Motor Selection · Blower Motor Protection · ★★
The blower motor (37kW) tripped out frequently on the thermal relay every 2~3 hours while running at a normal current of 61A (rated 65A). Inspection showed the motor temperature normal (65℃) and the load normal.
The thermal relay is a JR36-160 (setting current range 40~63A) with the setting at 57A (about 88% of the 65A rated current). But the thermal relay operates in a control cabinet at an ambient temperature of 45℃, while its operating characteristic is calibrated at a 40℃ reference. Using the temperature correction formula I_set_actual=I_set_calibrated×√((θ_ref-θ_amb)/(θ_ref-40))=57×√((60-45)/(60-40))=57×√(15/20)=57×0.866=49.4A. The actual setting is only 49.4A (referred to the standard 40℃ ambient) while the normal running current of 61A far exceeds 49.4A, so the thermal relay trips frequently. In addition the control cabinet ventilation is poor and the heat from the relay itself adds to the ambient temperature, further lowering the actual tripping current.
1) Thermal relay selection: the mid-point of the setting current range should equal the motor rated current
2) For a rated current of 65A select a thermal relay with a setting range of 56~71A (e.g. JR36-160/71)
3) Set the value at 65A×1.05=68A (allowing a 1.05 safety factor)
4) Control cabinet ambient temperature correction: for every 10℃ rise reduce the setting by 5%
5) At a 45℃ ambient the setting should be corrected to 68×(1-0.05×0.5)=66A
6) Or change to a motor protection relay (with temperature compensation, phase-failure protection and stall protection)
7) Improve cabinet ventilation: install an axial fan to bring the internal cabinet temperature below 35℃