E41-118 · Motor Selection · Outdoor Installed Motor · ★★
After a heavy rainstorm the insulation resistance of the outdoor motor dropped precipitately to zero and energising it caused an earth fault short circuit and trip. Teardown showed a large amount of water in the terminal box, with the terminals shorted and burnt.
The motor terminal box cable entry used an ordinary rubber sealing ring (IP54), leaving a 0.5~1mm gap between the cable and the ring. In heavy rain (rainfall 50mm/h) the rainwater seeped along the cable surface into the terminal box under wind pressure. Although a drain hole was provided in the bottom of the terminal box it was blocked by mud, leaving about 200ml of water. The impurity ions in the water formed a conductive path between the terminals, producing a three-phase short circuit. In addition the rubber gasket on the terminal box lid had aged (outdoor UV exposure plus temperature cycling), with its permanent compression set rising from 20% to 60%, so it lost its sealing function.
1) The protection class for an outdoor motor should be ≥IP55 (water-jet proof), IP65 recommended
2) Use a waterproof cable gland (PG type with an internal rubber sealing ring and lock nut) at the cable entry
3) Form a water loop (a U-shaped downward bend) in the cable at the entry to stop rainwater running along the cable into the box
4) Provide anti-clogging drain holes in the bottom of the terminal box (fit a stainless steel mesh)
5) Use silicone rubber for the terminal box lid gasket (weather resistance far better than NBR)