E41-156 · Motor Selection · Long-Distance Inverter Fed Motor · ★★★★
The inverter was 150m from the motor, and after three months of running the motor winding broke down to earth. Teardown showed clear overvoltage burn marks on the first turns of the winding with carbonised insulation material.
The inverter output PWM pulse produces a travelling-wave reflection when transmitted along a long cable. The pulse rise time is tr=0.1μs, the cable length L=150m and the wave speed v=150m/μs. When L>v×tr/3=5m the reflection must be considered. The reflection coefficient Γ=(ZL-Z0)/(ZL+Z0)=(motor impedance≈0 - cable characteristic impedance)/(≈0 + ...)≈1. The reflected voltage superposes at the motor terminal, and the peak voltage U_peak=U_DC+Γ×U_DC≈U_DC+U_DC=2U_DC. With an inverter DC bus voltage U_DC=√2×380≈537V, the peak voltage at the motor is U_peak≈1074V. The motor insulation withstand of 2×Un+1000=1760V appears to be satisfied, but the du/dt of the PWM pulse reaches 10kV/μs, and the cumulative damage to the insulation is far greater than with the mains frequency. The first turns experience the largest voltage gradient and break down first.
1) No reactor is needed when the inverter-to-motor distance is ≤50m
2) At 150m an output reactor (3% voltage drop) or a du/dt filter must be installed
3) Or select an inverter-specific motor (reinforced insulation, withstand ≥2.5kV)
4) Use a symmetrically shielded cable (matched characteristic impedance)
5) Shorten the rise time: raise the carrier frequency or install a sine-wave filter