E41-120 · Motor Selection · Long Cable Fed Motor · ★★★
When the motor 500m from the transformer was started the contactor chattered and failed to pick up, and the motor did not turn. The motor terminal voltage measured during starting was only 310V (rated 380V).
The supply cable is 3×50mm² aluminium, 500m long, with a 315kVA transformer and a short-circuit capacity of about 5MVA. The motor is 75kW with a starting current I_st=6×I_n=6×140=840A. The cable resistance is R=ρ×L/A=0.0283×500/50=0.283Ω and the reactance X=0.08×500/1000=0.04Ω (overhead installation). The voltage drop is ΔU=√3×I×(Rcosφ+Xsinφ)=1.732×840×(0.283×0.3+0.04×0.95)=1.732×840×(0.085+0.038)=1.732×840×0.123≈179V. The motor terminal voltage is U_motor=380-179=201V, only 53% of rated voltage. A contactor coil cannot stay picked up below 85% of rated voltage (323V). Since the starting torque T_st∝U², at 201V the starting torque is only 0.53²=0.28 times the rated starting torque, insufficient to overcome the load resisting torque.
1) Check the motor starting voltage drop: ΔU≤15% (during starting), ΔU≤5% (during running)
2) The 179V starting drop (47%) is far out of specification, so one of the following is required:
a) Increase the cable size: 50→120mm² aluminium (R falls to 0.118Ω and ΔU falls to about 85V)
b) Use a reduced-voltage start: star-delta or soft starter (starting current drops to 2.5 times rated and ΔU falls to 75V)
c) Install local reactive power compensation (capacitors switched in during starting, cosφ raised to 0.9)
d) Fit a stabilising module on the contactor coil (wide range 170~450V)
3) Upgrade the transformer: 315→500kVA
FT_12_Motor Selection Systematization