E41-159 · Motor Selection · Outdoor Open-Air Installed Motor · ★★★
After a typhoon with heavy rain the insulation resistance of the outdoor motor fell to zero and it tripped immediately on energising. Teardown showed a large amount of water inside the motor, with the stator winding shorted to earth.
The motor protection class was IP54 (dust proof plus splash proof), but the outdoor installation faces the wind and rain directly with no shielding, and during the typhoon a rain-laden airflow at 30m/s can easily penetrate the labyrinth sealing structure of an IP54 enclosure. The IP54 water test conditions are 10L/min flow, 100kPa pressure, 3m from the nozzle, for 5 minutes, whereas the actual typhoon conditions are far more severe (30mm/h rainfall plus 30m/s wind speed). In addition the gaps between the motor cooling fins and the terminal box suck in rainwater under negative wind pressure. The terminal box cable entry sealing ring had aged and the gap widened, allowing rain to seep in along the cable.
1) The protection class for an outdoor motor should be ≥IP55 (IP65 recommended)
2) IP65 provides protection against water jets (12.5L/min, 3m distance)
3) Fit a motor rain hood (stainless steel, enclosed on three sides)
4) Use a waterproof cable gland plus a cable water loop at the terminal box entry
5) Install the drain holes facing downward and check the sealing ring condition regularly