During the trial run of a new fan the motor rotated in the opposite direction to that required (the fan ran backwards), the airflow was only 30% of the design value and the motor current was high. The commissioning staff ran it under load for 2 hours without confirming the direction of rotation.
The direction of rotation of a three-phase induction motor depends on the phase sequence of the three-phase supply. When the new motor was wired the U/V/W phase correspondence was wrong (swapping any two phases reverses the rotation). With the fan running backwards the pressure and volume produced by the impeller drop sharply (airflow about 30% of forward running), the motor load lightens but cooling deteriorates (the self-ventilating fan also reverses). The commissioning staff ran it for 2 hours without confirming the direction, and the motor reached 95℃ through insufficient cooling. The correct procedure is to jog the motor to confirm the direction before the trial run, and for fan-type loads to confirm that the airflow direction agrees with the duct system.
1) Before the trial run of a new motor the direction of rotation must be confirmed by jogging (jog time ≤1s)
2) Mark the U/V/W phase sequence inside the motor terminal box
3) For fan-type loads the airflow direction must also be confirmed
4) Direction confirmation procedure: jog → observe the direction of rotation → compare with the marking
5) If the direction is wrong, swap any two supply phases