E41-165 · Motor Selection · High-Power Motor Frequent Starting · ★★★
When the 132kW motor was started directly the workshop lighting flickered and other equipment tripped. Measurement showed the bus voltage falling from 380V to 310V at the instant of starting (an 18% dip), beyond the 15% permitted.
The direct starting current is I_st=6.5×I_n=6.5×240=1560A. The transformer is 630kVA with 6% short-circuit impedance, giving a short-circuit capacity S_sc=S_n/Z_k=630/0.06=10500kVA≈10.5MVA. The starting apparent power is S_st=√3×U×I_st=1.732×380×1560≈1027kVA≈1MVA. The voltage drop is ΔU=S_st/S_sc=1/10.5≈9.5%, but adding the line impedance from the transformer to the motor (cable 0.05Ω) the total drop is about 18%. The sharp voltage dip prevents the contactor coils from holding (85%U_n=323V required, only 310V actual), so contactors on other equipment release and trip, and the lighting fixtures extinguish because of the voltage dip.
1) High-power motors (>75kW) should not be started directly; a reduced-voltage start must be used
2) Star-delta start: starting current falls to 1/3 (about 520A and the drop falls to 6%)
3) Soft starter: starting current can be limited to 2~3 times rated
4) Inverter start: starting current can be limited to below 1.5 times rated
5) If a direct start is unavoidable, verify ΔU≤15% and enlarge the transformer if this is not met