E41-317 · Motor Selection · Crane Hoisting Motor · ★★★★
The 22kW wound-rotor crane hoisting motor started 120 times per day, and after eight months the starting torque had fallen noticeably, so even a no-load start tripped on overload. Teardown showed multiple fractured rotor bars.
The rotor bars of a wound-rotor motor are subjected to enormous thermal stress and centrifugal force during frequent starting. Each start draws about twice rated current (wound rotor starting with series resistance) for about 3s, giving 120 starts per day × 8 months ≈ 28800 starts. The rotor bars (copper) develop thermal stress σ_th=E×α×ΔT=110000×17×10⁻⁶×150≈280MPa in the thermal cycles (copper expansion coefficient 17×10⁻⁶, temperature rise ΔT≈150℃). Under the combined action of 280MPa thermal stress and centrifugal force (about 50MPa) the copper rotor bars fatigue and fracture after about 3×10⁴ cycles. After the bars break the rotor resistance becomes unbalanced, current fluctuation increases and the remaining bars break more quickly still.
1) Upgrade the rotor bar material for frequently started motors: copper→copper-chromium alloy (tensile strength up by 50%)
2) Fit retaining rings at the rotor bar ends (reducing the centrifugal tension on the bars)
3) Extend the starting time (from 3s to 5s, reducing the thermal shock)
4) Use variable-frequency starting (starting current 1.5 times rated, heat reduced by 50%)
5) Periodically detect broken rotor bars (every 6 months by current spectrum analysis)