E41-325 · Motor Selection · Mobile Equipment Motor Phase Sequence · ★★★
After the supply connection point was changed, the motor of a mobile crusher ran in reverse (phase sequence error), and the fan ran for two hours in the reversed state, the insufficient airflow causing the equipment to overheat.
Each time mobile equipment connects to a different supply point the phase sequence of the three-phase supply may differ (the L1/L2/L3 to A/B/C correspondence is random). When the crusher fan motor runs backwards the airflow is about 30% of forward running and the cooling capability drops sharply. The motor current in reverse is about 15% higher than in forward rotation (different load characteristic), and combined with poor cooling the motor temperature rose from 70℃ to 110℃. The mobile equipment has no phase sequence protection fitted, and the operators did not confirm the direction of rotation after energising. The correct practice is to install a three-phase phase sequence relay at the main supply inlet of the equipment (cutting the control circuit when a phase sequence error is detected), or to install an automatic phase sequence converter (which corrects the sequence automatically).
1) Mobile equipment must have a phase sequence protection relay fitted (cut the control power on a phase sequence error)
2) Recommended phase sequence protector: XJ3-S (three-phase 380V, phase sequence plus phase failure protection)
3) After connecting to a new supply, jog the motor first to confirm the direction of rotation
4) Or install an automatic phase sequence converter (switches any two phases automatically to guarantee the correct output sequence)
5) Test the phase sequence protector regularly (once a month, simulating a phase sequence error to verify the operation)