E41-324 · Motor Selection · Motor Overload Protection Setting · ★★★★
When the conveyor drive motor (55kW) ran overloaded the thermal relay did not operate promptly and the motor winding burned out. The thermal relay setting current was 65A (62% of the motor rated current 105A) - too small? Actually the reverse is true.
The motor rated current is 105A, but the overload protection thermal relay setting current was set to 115A (1.1 times rated), so the setting is too high. The thermal relay operating characteristic is: at 1.2 times the setting current the operating time is about 2h, at 1.5 times about 3min, and at 6 times about 5s. When the conveyor jams the motor current rises to 200A (1.74 times the 115A setting), corresponding to an operating time of about 1min. But the jam only lasts 30s (the operator stops the machine by hand), so the thermal relay never operates. Running at the 200A stall current for 30s the winding temperature rise is θ=I²×R×t/(m×c)=200²×0.05×30/(50×400)=12℃ (R=0.05Ω, m=50kg, c=400J/kg·℃). A 30s stall raises the temperature by only 12℃, insufficient to trigger the protection. However the machine jams 10 times per day and the cumulative thermal effect builds up, so the motor gradually accumulates heat and the winding insulation finally fails under the cumulative high temperature.
1) Motor overload protection setting: I_set = I_n × 1.0 (infrequent starting) or I_n × 1.05 (frequent starting)
2) In this case the setting of 115A (1.1 times) is too high and should be 105A
3) Select an electronic overload relay (the operating curve can be programmed and the accuracy is higher)
4) Fit a motor winding temperature sensor (PT100, direct temperature detection is more reliable)
5) Jam detection: interlock a sudden current rise with its duration → immediate alarm and shutdown