E41-323 · Motor Selection · Vertical Motor Bearing Greasing · ★★
Two hours after the vertical motor (for a water pump) was greased and started running, oil stains appeared on the internal winding surfaces and the insulation resistance fell from 500MΩ to 10MΩ.
The vertical motor's bearings are at the top of the motor, and when greasing the operator grossly overfilled them (100% of the bearing housing) with no grease drain provided. The excess grease flowed slowly down the motor shaft under gravity, passing through the gap between the bearing and the end shield into the motor interior. The grease accumulated at the stator winding end and mixed with dust to form an oil sludge. The base oil in the grease seeped into the winding insulation, swelling the insulation material and causing the insulation resistance to fall sharply. At the same time the grease volatilised at the internal motor temperature of about 70℃, and the vapour condensed on the inner wall of the stator core and on the rotor, affecting heat dissipation and dynamic balance. Vertical motor bearings should have a grease drain at the lower part of the bearing housing, and the grease quantity must be strictly controlled.
1) Greasing quantity for vertical motor bearings: one third to one half of the internal bearing space (never fill it completely)
2) A grease drain must be provided at the lower part of the vertical motor bearing housing (with the outlet facing down)
3) After greasing, run at low speed for 30min and observe whether excess grease leaves the drain
4) Select a high-consistency grease that does not readily flow (NLGI#3)
5) The internal windings of the motor should be given oil protection (dip in three-component varnish)