E41-481 · Motor Selection · Motor Terminal Burnout · ★★★
After two years of running the terminals inside the motor terminal box were blackened and burnt, with a blue-purple high-temperature oxide colour on the terminal surfaces and carbonised insulation material.
The motor terminals (copper with tin plating, M8 bolts) were not tightened to the specified torque during installation (standard 20Nm, actual about 10Nm). The contact resistance is R_c=ρ/(π×r²)+R_oxide=1.7×10⁻⁸/(3.14×0.003²)+0.002≈0.0006+0.002=0.0026Ω. At the rated current I_n=200A the contact heating is P=I²×R=200²×0.0026=104W. This 104W of heating raises the temperature in the contact zone to about 150℃ (ambient 40℃), and the tin plating on the copper oxidises at 150℃ (the oxidation onset temperature of tin is about 120℃), forming SnO₂ oxide (resistivity about 10⁶Ω·m, an insulator). The contact resistance then increases further and the heating intensifies, creating a vicious circle. Eventually the temperature reaches about 300℃, the copper conductor anneals and softens (losing strength) and the terminal fractures.
1) Motor terminal tightening torque: M8 bolts at a standard 20Nm (use a torque wrench)
2) Apply conductive grease to the terminal surfaces before wiring (prevents oxidation and lowers the contact resistance)
3) Use copper crimp-type terminals (not soldered, to reduce the contact resistance)
4) Re-check the terminal torque hot 24h after running (re-tighten after thermal expansion)
5) Regularly check the terminal temperature with an infrared thermometer (a difference >10℃ requires action)
FT_12_Motor Selection Systematization