E41-484 · Motor Selection · Motor Insulation Resistance Testing · ★★★
The motor insulation resistance was tested with a 500V megohmmeter and the reading was 0.5MΩ (standard ≥1MΩ/kV=0.38MΩ), so it was judged that the insulation was unacceptable. In fact the winding temperature was 60℃ and the low reading was caused by the temperature.
Insulation resistance is closely related to temperature: for every 10℃ rise the insulation resistance falls by about 50%. At a winding temperature of 60℃ the insulation resistance is about 1/2^(40/10)=1/16 of the value at 20℃. Measured at 20℃ the value was 8MΩ, and at 60℃ only 0.5MΩ. But the standard requires insulation resistance ≥1MΩ/kV, which for a rated voltage of 380V is 0.38MΩ, so 0.5MΩ > 0.38MΩ and the machine is in fact acceptable. The operator did not know about the temperature correction (correction factor K_t=2^((t-20)/10)) and, having measured 0.5MΩ at 60℃, judged the insulation unacceptable, carrying out an unnecessary drying treatment and shutdown. The correct method is to correct the measured value to the equivalent at 20℃: R_20=R_t×K_t=0.5×2^((60-20)/10)=0.5×16=8MΩ, which passes.
1) Record the winding temperature when measuring the insulation resistance and correct for it
2) Temperature correction formula: R_20=R_t×2^((t-20)/10)
3) The measurement should be carried out immediately after power-off (the winding temperature is then close to the running temperature)
4) Use a 1000V megohmmeter (a 500V megohmmeter suits motors with a rated voltage ≤500V)
5) Measure the polarisation ratio (R60s/R15s≥1.3 indicates sound insulation)
FT_12_Motor Selection Systematization