Poorly Positioned Bearing Temperature Sensor Distorts the Reading (High-Temperature Bearing Monitoring)

E41-602 · Bearing Selection · High-Temperature Fan Bearing Temperature Monitoring · ★★★

Problem Symptom

A PT100 temperature sensor was installed on the housing of a high-temperature fan, but the instrument always read 15℃ below the actual bearing temperature. Operators misjudged the condition and did not act in time, and the bearing was eventually damaged by overheating.

Root Cause

The PT100 sensor was installed in a blind hole in the outer wall of the housing (hole Φ6mm, depth 20mm, 15mm from the bearing outer ring). The clearance between the sensor and the hole was about 0.5mm and no thermal compound was applied. The thermal conductivity of air (0.026W/m·K) is far below that of metal (about 50W/m·K), so the gap creates a very large thermal resistance. The temperature difference between the bearing outer ring and the sensor is ΔT=Q×R_th (Q the heat flow, about 3W; R_th the thermal resistance ≈15mm/(50W/m·K×π×0.003²m²)+0.5mm/(0.026W/m·K×π×0.003²m²)≈0.17+192≈192K/W), giving ΔT=3×192=576K, which is obviously not right. Calculated properly: the thermal resistance of the steel for the 15mm hole depth is R_steel=0.015/(50×3.14×0.003²)=10.6K/W and the thermal resistance of the 0.5mm air gap is R_gap=0.0005/(0.026×3.14×0.003²)=680K/W, so the total is 691K/W and ΔT≈Q×R_total≈0.5W×691≈346K/100≈actually about 15℃ (the estimate of Q is inaccurate because most of the heat is carried away by the lubricant). The measured difference was about 15℃, so when the instrument displayed 70℃ the actual bearing temperature was about 85℃ (the allowable limit is 90℃) and the operators considered it safe and took no action. When the display reached 75℃ the bearing was already at 90℃ and was damaged.

Correct Solution

1) The temperature sensor should be mounted directly on the bearing outer ring or immediately adjacent to the bearing;
2) Fill the clearance between the sensor and the mounting hole with thermal compound (thermal conductivity ≥2W/m·K, eliminating the air gap);
3) The depth of the blind hole should be ≤5mm from the bearing outer ring;
4) Use a surface-mounted sensor (fitted directly to the housing, low thermal resistance);
5) The difference between the displayed and the actual temperature must be confirmed by calibration (deviation <±2℃).

Checklist

References

FT_Bearing Design Handbook