E41-562 · Gearbox & Coupling Selection · Gearbox Lube Oil Cooler Fouling · ★★★★
Three years after start-up the heat transfer efficiency of the gearbox oil cooler (shell and tube) had fallen by 60% and the oil temperature rose from 55℃ to 75℃. On disassembly the cooling water tubes were found to be scaled about 1mm thick.
The cooling water side of the cooler tubes (brass, Φ12×1mm, length 3000mm) scaled up with CaCO₃ to about 1mm. The thermal conductivity of scale is about 0.5W/mK against 400W/mK for copper, so 1mm of scale is thermally equivalent to 800mm of copper tube. The total thermal resistance of the tube rose from 0.0001m²K/W (clean tube) to 0.002m²K/W (scaled tube), a 20-fold increase. The overall heat transfer coefficient K fell from 500W/m²K to about 100W/m²K. The heat transfer area is A=π×d×L×n=3.14×0.012×3×200≈22.6m² and the logarithmic mean temperature difference is ΔT_m≈20℃, so the heat transfer is Q=K×A×ΔT_m=100×22.6×20=45200W≈45.2kW. The gearbox heat loss is P_loss=500×(1-0.96)=20kW (96% efficiency), so 20kW < 45.2kW and the heat transfer capacity would still be sufficient. However, after three years of operation the cooling water flow had fallen by about 60% through the scaling (from 100L/min to 40L/min), so the actual heat transfer was about 40% of the clean value, i.e. about 45.2×0.4≈18kW, which is close to the 20kW of heat generation. The oil temperature rose from 55℃ to 75℃, and at that temperature the oxidation rate of the lubricant doubles.
1) Use softened cooling water (hardness ≤50mg/L) with corrosion and scale inhibitors;
2) Clean the cooler once a year (circulate a 5% citric acid solution through the tube bundle for 2h);
3) Fit a cooling water flow switch (alarm when the flow falls below 50L/min);
4) Cooler tube material: brass → stainless steel (corrosion resistant, smooth surface, less prone to scaling);
5) Keep a standby cooler so that it can be switched online for cleaning (no shutdown needed).
FT_13_Gearbox and Motor Matching Selection