E41-046 · Sensor Electrical Selection · Legacy-Equipment Retrofit Project · ★★
After installing a new pressure sensor, the PLC analog module channel reads 0 constantly; wiring is checked correct, sensor supply is normal (24 VDC), but the PLC receives no signal.
The legacy PLC analog module is 0~10 V voltage-input type (model FX2N-2DA), but the newly selected pressure sensor outputs a 4~20 mA current signal (two-wire). The analog module input impedance is about 200 kΩ (voltage type), while a current sensor needs a 250~500 Ω load resistor to work normally. Connecting the 4~20 mA current signal directly to the 0~10 V voltage-input module, the module input impedance is wrong, so the sensor cannot establish a normal operating point and outputs no signal.
① Before retrofit, confirm the original PLC analog module signal type (voltage/current) and range (0~10 V / ±10 V / 4~20 mA)
② Matching selection: sensor output type must match the PLC module signal type
③ If they do not match, there are three solutions:
a) Replace with a same-type sensor (simplest and most reliable)
b) Add a signal-isolation converter (e.g., 4~20 mA to 0~10 V isolated transmitter)
c) Parallel a 250 Ω precision resistor (converts 4~20 mA = 1~5 V, but uses only 50% of the 0~10 V range)
④ Recommended solution b: add signal-isolation transmitter ACT20P-CI-CO (4~20 mA input / 0~10 V output, accuracy 0.1%)
⑤ PLC module config: set channel range to 0~10 V; compensate the 4~20 mA-to-range conversion in the program