E41-110 · Sensor Electrical Selection · Hydraulic System Pressure Monitoring · ★★★
The hydraulic system pressure gauge reads 10 MPa, but the pressure-sensor reading fluctuates between 8 and 12 MPa; the pump outlet pressure is actually stable, yet the sensor reading is inaccurate.
The pressure sensor is mounted downstream of a 90° elbow at the hydraulic pump outlet (50 mm from the elbow), not on a straight pipe run. At the elbow the oil flow direction changes, producing secondary flow and vortices; the pressure at the sensor location contains not only static pressure but also a dynamic-pressure component. Dynamic pressure P_dynamic = ½ρv² = ½×900×5² = 11250 Pa ≈ 0.011 MPa. In addition, vortices downstream of the elbow cause pressure fluctuation of about ±0.5 MPa. The pressure sensor itself has 0.5%FS accuracy (16 MPa range, error ±0.08 MPa). Combined error = ±0.5 MPa (vortex fluctuation) + ±0.08 MPa (sensor accuracy) ≈ ±0.58 MPa, far exceeding the system requirement of ±0.1 MPa.
① Pressure-sensor mounting rule: place it on a straight run ≥5 pipe diameters from elbows/valves
② In this case: pipe diameter 20 mm, so the sensor should be on a straight run ≥100 mm from the elbow
③ If space is limited, add a damper or damping tube (to reduce pressure fluctuation)
④ Signal processing: PLC sampling filter (10-point moving average, 5 Hz cutoff)
⑤ Match sensor range: 16 MPa → 12 MPa (to improve resolution)
FT_33_Sensor Selection Guide