E41-109 · Sensor Electrical Selection · Long-Distance Sensor Installation · ★★
The sensor is installed 100 m from the PLC control cabinet. The 24 V supply is normal, but the signal read by the PLC is intermittent. Symptom: tests near the cabinet are normal, but the fault reappears after installation on site.
The sensor is a 3-wire type (24 VDC supply plus signal output) with 2×1.0 mm² power cable; a 100 m cable has resistance R = 2×100×0.0175/1.0 = 3.5 Ω. The sensor operating current is 200 mA, so the supply drop is ΔV = I×R = 0.2×3.5 = 0.7 V. At the sensor the voltage is 24−0.7 = 23.3 V, which seems normal (sensor operating range 18~30 V). However, the PLC discrete-input module requires a high level ≥15 V (for a 24 V system), and the signal line is also 100 m long with 3.5 Ω resistance; at sensor high output the signal current is about 15 mA and the signal-end drop ΔV_signal = 0.015×3.5 = 0.05 V, negligible. The actual cause: when a large on-site motor starts, the mains voltage sags to 200 VAC and the switching-power-supply output drops from 24 V to 20 V; the sensor-end voltage becomes 20−0.7 = 19.3 V, still within range. The real problem is that the signal line picks up interference voltage (common-mode) during motor start-up, and the PLC input module's limited common-mode rejection ratio (CMRR) causes signal misjudgment.
① For long distances (>50 m), use a 4~20 mA current loop for transmission (strong interference immunity)
② Or add a remote I/O module (acquire signals locally and transmit over a communication bus)
③ Upgrade the power cable: 1.0 mm² → 2.5 mm² (resistance drops to 1.4 Ω)
④ Use twisted-pair shielded cable for the signal line (twist pitch ≤25 mm)
⑤ Independent power supply: give the sensor its own switching power supply (isolated supply)