E41-108 · Sensor Electrical Selection · Storage-Tank Liquid-Level Detection · ★★★
When the liquid level is 100 mm from the sensor mounting face, detection fails and the system falsely reports an empty tank. Liquid is actually still in the tank, but the sensor outputs no signal.
An ultrasonic level sensor with a range of 0.5~8 m and a 0.5 m blind zone was selected (after emitting ultrasound the sensor has about 0.5 ms of ringing time during which echoes cannot be received). Mounted on the tank top, the liquid level is 100 mm < 500 mm (blind zone) from the sensor mounting face, so the echo returns during the sensor's ringing period and cannot be recognized. The blind-zone formula for an ultrasonic sensor is D_blind = v×t_ring/2 = 343 × 0.5×10⁻³ / 2 ≈ 0.086 m, but the manufacturer specifies a 0.5 m blind zone (including safety factor and transducer ringing time). The actual minimum detectable distance = blind zone + safety distance = 0.5 + 0.1 = 0.6 m.
① The ultrasonic sensor mounting height must exceed the blind zone plus safety distance
② Blind-zone check: sensor range lower limit ≤ minimum detectable distance
③ Mounting height: sensor-to-highest-level distance ≥ blind zone (≥0.5 m in this case)
④ Or select a small-blind-zone ultrasonic sensor (e.g., Siemens SITRANS Probe LR, 0.3 m blind zone)
⑤ Or switch to a radar level sensor (blind zone only 0.1 m)
⑥ Or use a guided-wave radar (no blind-zone issue)