E41-282 · Sensor Electrical Selection · Corrosive-Medium Pressure Detection · ★★★★
A diaphragm pressure sensor measuring chlorinated wastewater (Cl⁻ 5000ppm, pH=3) showed 5%FS zero drift after 2 months, with readings biased high.
The pressure sensor diaphragm is 316L stainless steel, which suffers pitting corrosion in chlorinated acidic wastewater. Cl⁻ destroys the passive film (Cr₂O₃) on the 316L surface, producing pitting pits on the diaphragm (diameter 0.1~0.3mm, depth ~0.02mm). The pits change the diaphragm's elastic modulus; under the same pressure the diaphragm deforms more, biasing the output high (positive zero drift 5%FS). Pitting also makes the diaphragm thickness uneven, creating stress concentration and a long-term rupture risk. The corrosion rate is about 0.01mm/month; after 2 months the diaphragm thickness drops from 0.1mm to about 0.08mm (20% thinning).
① Diaphragm for corrosive medium should use Hastelloy C276 (resistant to Cl⁻ pitting)\n② Or add an anti-corrosion isolation diaphragm (PTFE membrane + silicone-oil fill, fully isolating the medium)\n③ Diaphragm-type pressure sensor (oil-filled isolation, 316L diaphragm + PTFE coating)\n④ Periodic calibration (every 2 weeks; corrosive medium shortens the calibration interval)\n⑤ Add a flush ring (online flushing at the sensor front, reducing scaling and corrosion)
FT_33_Sensor Selection Guide