E41-283 · Sensor Electrical Selection · Space-Constrained Flowmeter Installation · ★★★
The electromagnetic flowmeter is installed only 2D from the upstream elbow (D = pipe diameter), giving a measurement error of ±5% (specification ±0.5%). The upstream straight-run requirement is ≥5D.
The electromagnetic flowmeter works on Faraday's law of electromagnetic induction and requires a fully developed turbulent velocity profile in the measuring section. An upstream elbow causes velocity-profile distortion (secondary flow); at 2D downstream of the elbow, the maximum velocity-profile deviation reaches ±15%. The flowmeter's velocity-profile correction factor is calibrated at the factory for an ideal profile, so under a distorted profile the correction error Δ = K_actual/K_cal - 1 ≈ 5%. With upstream straight run below 5D, error decreases as straight-run length increases: 2D→5% error, 5D→1% error, 10D→0.3% error.
① Electromagnetic flowmeter upstream straight run ≥5D, downstream ≥2D\n② When space is limited, add a flow conditioner (tube-type, equivalent to 3D straight run)\n③ Install the conditioner immediately upstream of the flowmeter\n④ Use a dual-straight-run flowmeter (insensitive to velocity profile)\n⑤ Field calibration correction (calibrate with actual flow to compensate installation error)