E41-443 · Sensor Electrical Selection · Ultrasonic Sensor Transducer Aging · ★★★
An ultrasonic level sensor in continuous service for 3 years had its detection range drop from 8m to 4m; the liquid level at 5m could not be detected, and it falsely reported an empty tank.
The ultrasonic sensor's piezoelectric transducer (PZT-5 piezo ceramic) undergoes fatigue degradation under long-term high-frequency vibration (about 40kHz, 24h/day×3 years≈26000h). The piezoelectric constant d₃₃ (charge sensitivity) drops from an initial 400pC/N to about 280pC/N (a 30% decrease). The transmit power drops 30%, and the echo signal strength drops about 60% (two-way attenuation). The sensor's internal amplifier gain is fixed (non-adjustable); once the echo strength drops 60%, the echo at 5m falls below the detection threshold and cannot be recognized. The transducer degradation rate is about 10%/year, so after 3 years the cumulative degradation is about 30%; the effective detection range is proportional to the square root of transmit power, √(0.7)≈0.84, giving 8m×0.84≈6.7m. The actual 4m indicates that besides transducer degradation there are other factors (environmental dust adhering to the transducer surface and absorbing sound waves).
① Ultrasonic sensor transducer life: about 3~5 years of continuous operation (depending on duty and environment)\n② Clean the transducer surface periodically (every 6 months with non-woven cloth + alcohol)\n③ Use a sensor with automatic gain control (AGC) (automatically compensating transducer degradation)\n④ Sensor range selection: choose 1.5× the actually required distance (leaving margin for degradation)\n⑤ Once the transducer degrades, the sensor must be replaced (the transducer is not separately replaceable)
FT_33_Sensor Selection Guide