E41-442 · Sensor Electrical Selection · Pipe Temperature Sensor Thermal Resistance · ★★★
The temperature sensor on a steam pipe (260℃) responds with severe lag (about 30s); the control system cannot adjust the valve opening in time, and the temperature fluctuates ±15℃.
The temperature sensor (Pt100 platinum RTD, Φ6×100mm probe) is mounted inside a thermowell on the pipe (stainless steel, Φ12×150mm). The gap between sensor and thermowell (about 0.5mm) is not filled with a thermal medium (air thermal conductivity 0.026W/mK). The total thermal resistance from pipe wall to sensor probe is R=R_wall+R_gap+R_sensor. The thermal resistance of the air gap is R_gap=ln(r2/r1)/(2π×L×K_air)=ln(6/5)/(2π×0.1×0.026)≈16.5K/W. The sensor heat capacity is C_sensor=m×c=0.02×400=8J/K (sensor mass about 20g, specific heat 400J/kg·K). The time constant is τ=R×C=16.5×8=132s. Raising the steam temperature from 250℃ to 260℃ takes about 5s (valve adjustment), but the sensor needs about 3τ=396s to stabilize and indicate the true temperature, so the response lags severely.
① Fill thermal grease between the temperature sensor and the thermowell (thermal conductivity 2W/mK, thermal resistance drops to 0.2K/W, time constant τ≈1.6s)\n② Use a thin-probe sensor (Φ3mm, lower heat capacity, faster response)\n③ Or use a surface-mount temperature sensor (attached directly to the pipe outer wall, no well thermal resistance)\n④ Thermowell material: stainless steel→copper (thermal conductivity 20× higher)\n⑤ Enable derivative action in the PID controller (anticipatory control based on temperature rate of change)