E41-447 · Sensor Electrical Selection · Cold-Storage Photoelectric Sensor Fogging · ★★★
The photoelectric sensor inside the cold store (-20℃) fogs up rapidly on its lens when the door opens, failing for about 10min (recovering after the fog clears). It false-triggers several times a day.
The cold store is at -20℃ with a relative humidity of about 60%. When the door opens, warm humid outside air (30℃, RH80%) enters the cold store and condenses into fog on the cold lens surface of the sensor inside (temperature difference 50℃, dew point about 26℃, lens surface temperature -20℃). The water fog reduces laser transmittance from 90% to about 10% (fog droplets 1~10μm in diameter strongly scatter the laser), so the receiver cannot get enough light intensity and the sensor output turns off. About 10min after the door opens, the cold-store air reaches thermal equilibrium with the cold surface (the lens temperature drops to -20℃ and the moisture in the air frosts on the lens instead of fogging); frost scatters the laser less than fog droplets (frost is more uniform), so the light intensity recovers to about 60% and the sensor starts working again. But the frost layer keeps thickening (the longer the door stays open, the more moisture enters), finally icing over and causing total failure.
① Cold-storage photoelectric sensors should be the type with lens heating (heating power 5~10W, temperature rise ≥30℃)\n② Or add an air curtain (forming a dry-air barrier in front of the sensor to keep moisture off the lens)\n③ Mount the sensor outside the cold store (detect into the store through a glass window with heating to prevent fogging)\n④ Or use a radar sensor (microwaves penetrate fog/frost, so it is unaffected)\n⑤ Fit the cold-store door with a quick-closing mechanism (shortening door-open time and reducing moisture ingress)
FT_33_Sensor Selection Guide