Knowledge Base › Selection Error Cases › Pressure sensor poorly positioned causing low readings (pipe elevation difference)

Pressure sensor poorly positioned causing low readings (pipe elevation difference)

E41-451 · Sensor Electrical Selection · Pressure Sensor Mounting-Position Elevation Difference · ★★★

Problem Description

The pressure sensor is mounted at the highest point of the pipe (10m above the pump outlet); its reading is 0.12MPa lower than the pump outlet pressure, and the operator mistakenly assumed the pump pressure was insufficient.

Root Cause

The pressure sensor is mounted at the highest point of the pipe (elevation +10m), and the pump outlet pressure is set at 0.6MPa. The medium in the pipe is water (density 1000kg/m³); the static pressure difference from the pump outlet to the sensor mounting point is ΔP=ρ×g×h=1000×9.8×10=98000Pa≈0.098MPa≈0.1MPa. With a pump outlet pressure of 0.6MPa, the sensor reading should be 0.6-0.1=0.5MPa. The actual sensor reads 0.48MPa (0.02MPa below the calculated value, caused by pipe friction loss). The operator did not account for the static pressure difference and took the sensor reading of 0.48MPa as the pump outlet pressure (assuming the pump pressure was insufficient), trying to raise the relief-valve setting (increasing system pressure), which caused unnecessary adjustment. In fact the pump outlet pressure is normal (0.6MPa); the low sensor reading is caused by the mounting position.

Corrective Solution

① The pressure sensor should be mounted close to the measurement point (≤1m from the pump outlet)\n② When mounting below a pipe elevation difference, apply height compensation (subtract ρ×g×h)\n③ Or use a differential-pressure sensor (measuring the pressure difference between two points, compensating static pressure)\n④ Mark the sensor mounting position on the operator panel (height difference from the pump outlet)\n⑤ Automatically compensate in the PLC control (enter the sensor mounting height, automatically correcting the reading)

Checklist

Reference

FT_33_Sensor Selection Guide

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »