Flow sensor internal-wall scaling causing measurement deviation (circulating cooling water)

E41-452 · Sensor Electrical Selection · Cooling-Water Flow Sensor Scaling · ★★★

Problem Description

After 2 years of use in a circulating cooling-water system, the electromagnetic flowmeter's reading drifted from 100m³/h to 85m³/h (the actual flow should be unchanged). Inspection found scale adhering to the inner wall (about 0.5mm thick).

Root Cause

The electromagnetic flowmeter's measuring electrodes contact the fluid directly, and scale (mainly CaCO₃, conductivity about 0.01S/m) deposits on the electrode surfaces, reducing the electrodes' effective contact area. When the electrodes are about 50% covered by scale, the measurement-signal amplitude drops about 40% (the scale's dielectric constant ε_r≈20 versus water's ε_r≈80; the induced magnetic signal the electrode senses through the scale is weakened). The theoretical relation between the flowmeter output signal and flow velocity is U=K×B×D×v (K = coefficient, B = magnetic flux density, D = pipe diameter, v = flow velocity); scale coverage changes the K value (about -15%). The flowmeter's factory-calibrated K value was set under clean conditions, so the actual K value after scale deposits deviates from the calibrated value, giving a measurement error of about 15% (100→85m³/h).

Corrective Solution

① Clean electromagnetic flowmeters periodically when used with scaling media (once a year, chemical cleaning)\n② Add auto-cleaning electrodes (ultrasonic cleaning or mechanical brush cleaning)\n③ Upgrade the flowmeter lining material: PTFE→PFA (smoother surface, less prone to scale adhesion)\n④ Add a scale inhibitor to the water (controlling water quality, reducing scale formation)\n⑤ Or use an ultrasonic flowmeter (clamp-on type; the sensor is outside the pipe, unaffected by internal scaling)

Checklist

Reference

FT_33_Sensor Selection Guide